Kaji Eksperimental Pengaruh Penggunaan TXV dan Pipa Kapiler Terhadap Kinerja Sistem Mini Chiller untuk Aquascape

Ekspesimental Study The Utilyzation of TXV and Capilary Tube to Performance of Mini Chiller System for Aquascape

Tugas Akhir, 002 / 2020 / RTU
Undergraduate Theses from JBPTPPOLBAN / 2021-11-29 09:37:36
Oleh : Adela Meliawati Gunawan - 171611001 (adela.meliawati.tptu17@polban.ac.id)
Dibuat : 2021-11-29, dengan 4 file

Keyword : Mini Chiller, TXV, Capillary Tube, COP, System Efficiency, Aquascapes.
Subjek : Mini Chiller, TXV, Pipa Kapiler, COP, Efisiensi Sistem, Aquascapes.

Sistem Mini Chiller untuk Aquascape ini merupakan sistem kompresi uap sederhana yang dibutuhkan untuk mendinginkan air pada Aquascape yang harus dijaga pada temperatur 18-20℃. Pada tugas akhir ini, dilakukan pengujian untuk membandingkan alat ekspansi TXV tipe Danfoss T2 dan pipa kapiler diameter 0,031″ dengan panjang 0,59 m, untuk mendapatkan alat ekspansi yang lebih efektif pada sistem mini chiller untuk aquascape. Setelah dilakukan proses pengambilan dan pengolahan data dapat diketahui bahwa, sistem dengan alat ekspansi TXV didapatkan chilling time 70 menit, dengan rata-rata dalam keadaan steady didapatkan COPaktual sebesar 3,69, COPcarnot sebesar 6,06, dan nilai efisiensi sebesar 61%, sedangkan saat menggunakan pipa kapiler chilling time selama 100 menit, dengan rata-rata dalam keadaan steady didapatkan COPaktual sebesar 3,4, COPcarnot sebesar 4,51, dan nilai efisiensi sebesar 76%. Dari pengambilan dan pengolahan data yang didapatkan sistem mini chiller untuk aquascape ini lebih cocok menggunakan alat ekspansi pipa kapiler.

Deskripsi Alternatif :

This Mini Chiller System for Aquascape is a simple vapor compression system needed to cool water in the Aquascape which must be maintained at a temperature of 18-20 ℃. In this final project, a test was conducted to compare the TXV expansion tool Danfoss T2 type and capillary tube diameter of 0.031″ with a length of 0.59 m, to obtain a more effective expansion tool for the mini chiller system for aquascape. After the data retrieval and processing process is carried out, it can be seen that the system with the TXV expansion device has a chilling time of 70 minutes, with an average in a steady state the COPactual is 3.69, COPcarnot is 6.06, and the efficiency value is 61%, while When using the capillary tube chilling time for 100 minutes, with an average in a steady state, the COPactual is 3.4, COPcarnot is 4.51, and the efficiency value is 76%. From the data collection and processing, the mini chiller system for aquascape is more suitable for using a capillary tube expansion device.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakErlin Arvelina
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorerlin.arvelina@polban.ac.id
E-mail CKOerlin.arvelina@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: A. P. Edi Sukamto, S.T., M.T.


    Pembimbing 2: Triaji Pangripto Pramudantoro, S.T., M.Eng., Editor: Muhammad Abdillah Islamy, S.Pd

Download...