Analisa Kandungan Harmonisa Pada Instalasi Listrik Di Gedung Hotel Santika Garut

Harmonics Content Analysis in Electrical Installations in the Hotel Santika Garut Building

Tugas Akhir, 004 / 2019 / TLI
Undergraduate Theses from JBPTPPOLBAN / 2020-03-19 10:56:02
Oleh : Andri Anshori - 161321004 ( anshoriandri@gmail.com )
Dibuat : 2020-03-19, dengan 4 file

Keyword : Harmonics, THDi, THDv, power analyzer, and passive filters
Subjek : Harmonisa, THDi, THDv, alat ukur power analyzer, dan filter pasif.

Harmonisa merupakan gangguan yang terjadi pada sisitem distribusi tenaga listrik akibat terjadinya distorsi gelombang arus dan tegangan. Distorsi ini disebabkan oleh beban non-linier, sehingga bentuk gelombang tegangan dan arusnya menjadi tidak sinusoidal murni. Semakin besar nilai kandungan harmonisa pada suatu sistem tenaga listrik maka semakin menurun kualitas daya pada sistem listrik tersebut. Pengukuran menggunakan alat ukur power analyzer yang merupakan cara untuk dapat mengetahui nilai kandungan harmonisa arus dan tegangan sebagai parameter baik atau buruknya kualitas daya pada sistem tenaga listrik. Tujuannya adalah untuk mengetahui harmonisa arus dan tegangan di Hotel Santika Garut. Setelah mendapatkan hasil pengukuran maka dilakukan analisa dengan menggunakan perhitungan dan perbandingan terhadap standar IEEE 519-2014. Hasil pengukuran pada panel LVMDP Hotel Santika Garut menunjukan bahwa nilai kandungan harmonisa arusnya melebihi standar 15% dengan nilai THDi nya yaitu 17,45%, 16,37%, dan 15,74%. Sedangkan untuk nilai kandungan harmonisa tegangannya sesuai dengan standar 5% dengan nilai THDv nya adalah 2,41%, 2,47% dan 2,40%. Maka untuk kandungan nilai harmonisa arus yang melebihi standar, untuk direkomendasikan memakai filter pasif yaitu dengan menggunakan filter pasif single tunned filter.

Deskripsi Alternatif :

English: Harmonics is a disturbance that occurs in the electric power distribution system due to the distortion of current and voltage waves. This distortion is caused by a non-linear load, so the voltage and current waveforms are not pure sinusoidal. The higher the reserve value in the power system, the lower the quality of the power system. Measurements using an analyzer power measuring device which is a way to determine the current and voltage harmonic reserve value as a parameter of good or bad power quality in the electric power system. The aim is to understand the harmonics of current and voltage at the Hotel Santika Garut. After getting the measurement results, an analysis is performed using calculations and comparing against the IEEE 519-2014 standard. The measurement results on the LVMDP Hotel Santika Garut panel showed an average value of 15% with a THDi value of 17.45%, 16.37%, and 15.74%. While for harmonic balance value according to standard 5% with THDv value is 2.41%, 2.47% and 2.40%. So for the reserve value of current harmonics that exceeds the standard, for the use of passive filters is recommended by using a single filter passive filter.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakHelmi Purwanti
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorhelmi.purwanti@polban.ac.id
E-mail CKOhelmi.purwanti@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: Ir. Abdullah Asegaf, M.T.


    Pembimbing 2: Yudi Prana Hikmat, S.T., M.T., Editor: Muhammad Abdillah Islamy, S.Pd

Download...