Path: Top > Tugas Akhir - D3 > Jurusan Teknik Refrigerasi dan Tata Udara > Program Studi Teknik Refrigerasi dan Tata Udara > 2013

Analisis Pengaruh Bypass Ducting dan Variasi Beban Terhadap Kinerja Model Sistem Tata Udara Presisi Untuk Ruang Server Dengan Pengontrolan pada Damper

Analysis of Bypass Ducting and Load Variation Influence on Performance of Precision Air Conditioning For Server Room Model With Use Damper Control

Tugas Akhir, 078 / 2013 / RTU
Undergraduate Theses from JBPTPPOLBAN / 2017-04-25 15:35:36
Oleh : Andri Ishak Awalujan - 101611001 (andriishak@yahoo.co.id)
Dibuat : 2017-04-25, dengan 4 file

Keyword : AC Presisi, Distribusi Udara, Ruangan Server
Subjek : Precision Air Conditioning (PAC), Air Distribution, Server Rooms

Aplikasi sistem refrigerasi dan tata udara tidak hanya digunakan untuk kenyamanan termal di suatu ruangan saja, tapi juga merambah ke berbagai industri, termasuk untuk mengkondisikan data center (server) yaitu dengan menggunakan Precision Air Conditioning (PAC). Untuk lebih mempermudah dalam mempelajari hal tersebut, maka dibuat model sistem tata udara presisi untuk ruang server. Dalam model sistem tata udara ini, temperatur ruangan dijaga pada kondisi 20oC (±1). Adapun untuk menjaga temperatur tersebut, dilakukan pengontrolan pada bukaan damper untuk bypass ducting. Untuk mengetahui pengaruh dari perubahan temperatur dan keandalan dari bypass ducting tersebut, maka dibuat tugas akhir dengan judul "Analisis Pengaruh Bypass Ducting dan Variasi Beban Terhadap Kinerja Model Sistem Tata Udara Presisi untuk Ruang Server dengan Pengontrolan pada Damper". Adapun maksud dan tujuan penyusunan tugas akhir ini yaitu untuk memahami pengaruh penggunaan Bypass Ducting pada saluran udara terhadap kinerja sistem model tata udara presisi yang dibuat, dan memahami pengaruh variasi beban terhadap kinerja sistem dan distribusi udara. Setelah dilakukan pengambilan data dan melakukan analisis, maka dapat disimpulkan bahwa dengan menggunaan Bypass ducting dapat menurunkan temperatur udara mixing dari 21,73oC menjadi 17,91oC. Hal ini menyebabkan kerja sistem pendingin akan menjadi lebih ringan, dan menaikan nilai efisiensi sistem refrigerasi, yaitu dari 72,51% menjadi 76,78% ketika thermostat untuk mengatur heater pada model server di-setting 50oC, dan 75,77% menjadi 78,43 % ketika di-setting 80oC. Selain itu, semakin tinggi nilai beban pada ruangan, menyebabkan waktu pendinginan akan semakin bertambah dari 5 menit menjadi 7 menit ketika termostat disetting pada 50oC dan 80oC. Kata kunci: AC Presisi, Distribusi Udara, Ruangan Server.

Deskripsi Alternatif :

Application of RHVAC system not only used for thermal comfort in rooms, but also penetrated into various industries, including to condition the data center(server) that using the Precision Air Conditioning (PAC). To facilitate in learning about that, it made PAC model for server rooms. In this RHVAC system model, the room's temperature is conditioned on 20oC (±1). As for condition the room's temperature, its with controlling the opening of damper for bypass ducting. To determine the influence of temperature changes and reability of the bypass ducting, then be made the final project with the title "Analysis of Bypass Ducting and Load Variation Influence on Performance of Precision Air Conditioning for Server Room Model with Use Damper Control". The intent and the purpose of preparation this final project is to understand the influence of bypass ducting in the airways on performance of this RHVAC system model and to understand the influence of load variation on performance of this system and its air distribution. After the data collection and analysis process,it can be concluded that by using Bypass ducting, it will decrease the mixing air temperature from 21,73oC to 17,91oC. This causes the work of refrigeration system will be lighter, and increase the efficiency of this refrigeration system, ie from 72,51% to 76,78% when the thermostat of heater in server model is set on 50oC, and from 75,77% to 78,43% as at 80oC setting. Moreover, the higher of the room load value, the chilling time will be increased from 5 minutes to 7 minutes when the thermostat be set at 50oC and 80oC. Keywords: Precision Air Conditioning (PAC), Air Distribution, Server Rooms.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakHelmi Purwanti
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorhelmi.purwanti@polban.ac.id
E-mail CKOhelmi.purwanti@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: Muhammad Nuriyadi, S.T., M.Eng.

    Pembimbing 2: Luga Martin Simbolon, S.T., M.Sc., Editor: Erlin Arvelina

Download...