Penggunaan Tuned Mass Damper Pada Struktur Gedung Call Center Telkom-Kota Bandung

The Application of Tuned Mass Damper on Call Center Telkom Building Structure-Bandung

Tugas Akhir, 028 / 2017 / TPPG
Undergraduate Theses from JBPTPPOLBAN / 2018-09-03 15:05:26
Oleh : Arlianis Anina - 131144032 (arlianina.anina@gmail.com)
Dibuat : 2018-02-19, dengan 4 file

Keyword : Tuned Mass Damper, Gempa El Centro, Gempa Landers, Gempa Irpinia, Analisis Dinamik Riwayat Waktu, Simpangan Antar Lantai, Gaya Geser Dasar, Periode Getar
Subjek : Tuned Mass Damper, El Centro Earthquake, Landers Earthquake, Irpinia Earthquake, Dynamic Analysis of Time History, Story Drift, Base Shear Force, Vibration Period

Peraturan yang berlaku sekarang telah mengizinkan struktur bangunan mengalami kerusakan yang parah akibat gempa kuat, sekali seumur hidup bangunan. Namun, biaya perbaikan untuk struktur bangunan yang rusak terhitung tinggi. Karena itu dikembangkan teknologi untuk bangunan tahan gempa, yaitu dengan menggunakan sistem peredam gempa. Sistem peredam gempa memiliki berbagai jenis, salah satunya adalah Tuned Mass Damper. Tuned Mass Damper pada umumnya diletakkan pada struktur lantai teratas, dan bekerja dengan menyelaraskan frekuensi peredam dengan frekuensi struktur utama saat menerima gaya gempa. Menganalisis sistem Tuned Mass Damper dilakukan dengan menggunakan analisis dinamik riwayat waktu. Analisis ini juga dilakukan dengan menggunakan jenis gempa yang berbeda, yaitu Gempa El Centro, Landers, dan Irpinia. Menganalisis dengan gempa yang berbeda bertujuan untuk mengetahui sistem tersebut telah sesuai atau tidak untuk setiap karakteristik gempa. Analisis dilakukan dengan membandingkan nilai simpangan antar lantai, nilai gaya geser dasar, serta periode getar pada struktur yang menggunakan atau tanpa sistem Tuned Mass Damper. Berdasarkan hasil analisis yang telah dilakukan, sistem Tuned Mass Damper yang paling efektif adalah dengan massa 5% dan panjang lengan 1 meter. Namun, sistem ini tidak selalu sesuai dengan setiap karakteristik gempa yang ada. Selain itu, sistem Tuned Mass Damper tidak hanya mereduksi gaya gempa yang diterima oleh struktur tetapi pada kondisi tertentu sistem ini dapat memperparah gaya gempa. Selain dilakukan analisis, dilakukan juga metode pemasangan sistem Tuned Mass Damper pada bangunan eksisting. Kata kunci: Tuned Mass Damper, Gempa El Centro, Gempa Landers, Gempa Irpinia, Analisis Dinamik Riwayat Waktu, Simpangan Antar Lantai, Gaya Geser Dasar, Periode Getar.

Deskripsi Alternatif :

For this time Indonesian code has allowed building structures to be severely damaged by strong earthquake, once in a lifetime of building. But, the repair cost for damaged building structure are high. Therefore, technology for earthquake resistant building has been developed, such as earthquake damper system. Earthquake damper system has various types, one of them is Tuned Mass Damper. Tuned Mass Damper generally was placed on the highest floor, and works by aligning the frequency of the damper with the frequency of the main structure when received a seismic force. In this research, analyzing the system of Tuned Mass Damper was performed by using a dynamic analysis of time history. The analysis also performed by using a different a types of earthquakes, that is El Centro Earthquake, Landers Earthquake, and Irpinia Earthquake. Analyzing with different earthquakes has a purpose to find out whether the system is suitable or not for every earthquake characteristics. The analysis was performed by comparing the story drift, base shear force, and vibration period on structures which using or without Tuned Mass Damper system. Based on the results of analysis, the most effective Tuned Mass Damper system is with a mass of 5% of the total building mass and a length of rope is 1 meter. But, this system doesn't always correspond with every earthquake characteristics. Besides, in some cases Tuned Mass Damper system is not only reduce the seismic forces, but also can aggravate the seismic force. In addition to the analysis, the method of installation of Tuned Mass Damper system in existing building is also presented. Keywords: Tuned Mass Damper, El Centro Earthquake, Landers Earthquake, Irpinia Earthquake, Dynamic Analysis of Time History, Story Drift, Base Shear Force, Vibration Period.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakHelmi Purwanti
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorhelmi.purwanti@polban.ac.id
E-mail CKOhelmi.purwanti@polban.ac.id

Print ...

Kontributor...

  • Pembimbing: Dr. Ir. Riawan Gunadi, M.T., Editor: Erlin Arvelina

Download...