Analisis Kinerja Pengkondisi Udara Menggunakan R410A Akibat Pengaruh Variasi Suhu Udara Lingkungan

Analysis Performance Of Air Conditioning Using R410A Influence By Variation Ambient Temperature

Skripsi, 006 / 2018 / PTU
Undergraduate Theses from JBPTPPOLBAN / 2019-01-10 10:27:14
By : Dina Natasya Viorika - 141624007 (dinatasya12@gmail.com)
Created : 2019-01-10, with 4 files

Keyword : Refrigeran 410A, AC split, Kapasitas pendinginan, Daya input, COP
Subject : Refrigerant 410A, split AC, Cooling capacity, Input power, COP

Suhu udara lingkungan diberbagai daerah berbeda dengan daerah lainnya, mulai dari yang sejuk hingga yang panas. Kondisi udara lingkungan akan mempengaruhi kinerja pengkondisi udara. Saat ini AC split menggunakan refrigeran R410A adalah pengkondisi udara yang paling banyak digunakan di Indonesia. Refrigeran R410A ini adalah refrigeran alternatif pengganti R22. Karena suhu udara lingkungan berpengaruh pada kinerja pengkondisi udara maka pada penelitian ini dilakukan pengamatan pengaruh variasi suhu lingkungan pada suhu 27,8⁰C; 28,4⁰C; 32,5⁰C dan 33,8⁰C untuk mengetahui kapasitas pendinginan, daya input kompresor, COP serta konsumsi energi listrik. Analisis dilakukan dengan mengambil data suhu supply, suhu return, suhu lingkungan, kecepatan udara, tegangan dan arus. Berdasarkan pengujian, data menunjukan bahwa terjadi peningkatan daya input akibat peningkatan suhu udara lingkungan pada 27,8⁰C; 28,4⁰C; 32,5⁰C dan 33,8⁰C adalah 0,684 kW, 0,698 kW, 0,707 kW dan 0,729 kW. Dari data yang didapat bahwa akan menurunkan kapasitas pendinginan yaitu 2,629 kW; 2,591 kW; 2,551 kW dan 2,519 kW. Penurunan COP pada suhu udara lingkungan yaitu 3,845; 3,709; 3,610; dan 3,454. Sedangkan kenaikan konsumsi energi listrik adalah 7,12 kWh, 7,28 kWh, 7,36 kWh dan 7,6 kWh. Pada penelitian ini dapat disimpulkan pada suhu lingkungan 27,8⁰C hingga 33,8⁰C bahwa rata-rata penurunan kapasitas pendinginan tiap 1⁰C adalah 0,71% sedangkan rata-rata kenaikan daya input 1,07%; rata-rata penurunan COP sebesar 1,76% dan kenaikan konsumsi energi listrik rata-rata 1,10%. Kata kunci : Refrigeran 410A, AC split, Kapasitas pendinginan, Daya input, COP.

Description Alternative :

The air temperature of the environment in different regions is different from other areas, from the cool to the hot. Environmental air conditions will affect the performance of air conditioners. Currently split air conditioner using R410A refrigerant is the most widely used in Indonesia. This R410A refrigerant is an alternative replacement for R22. Since the air temperature of the environment has an effect on the performance of the air conditioner, this observation is done to observe the effect of the ambient temperature variation of 27,8⁰C; 28,4⁰C; 32,5⁰C and 33,8⁰C to determine the cooling capacity, compressor input power, COP and electrical energy consumption. The analysis is by taking the temperature of supply data, temperature return, ambient temperature, air velocity, voltage and current. Based on the test, the data show that there is an increase input power due to the increase of environmental air temperature at 27,8⁰C; 28,4⁰C; 32,5⁰C and 33,8⁰C were 0,684 kW, 0,698 kW, 0,707 kW and 0,729 kW. From the data obtained that will reduce the cooling capacity is 2,629 kW; 2,591 kW; 2,551 kW and 2,519 kW. Decrease in COP at ambient air temperature is 3,845; 3,709; 3,610; and 3,454. While the increase in electrical energy consumption is 7,12 kW; 7,28 kWh; 7,36 kWh and 7,6 kWh. In this study it can be concluded at the ambient temperature of 27,8⁰C to 33,8⁰C that the average decrease in cooling capacity per 1⁰C is 0,71% while the input power increase 1,07%; average COP decrease of 1,76% and an average increase in electrical energy consumption of 1,10%. Keywords: Refrigerant 410A, split AC, Cooling capacity, Input power, COP.

Give Comment ?#(0) | Bookmark

PropertyValue
Publisher IDJBPTPPOLBAN
Organization
Contact NameHelmi Purwanti
AddressJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
CityBandung
RegionJawa Barat
CountryIndonesia
Phone022 201 3789 ext. 168, 169, 239
Fax022 201 3889
Administrator E-mailhelmi.purwanti@polban.ac.id
CKO E-mailhelmi.purwanti@polban.ac.id

Print ...

Contributor...

  • Pembimbing 1: Ir. Sumeru, M.T., Ph.D.

    Pembimbing 2: Triaji Pangripto Pramudantoro, S.T., M.Eng., Editor: Erlin Arvelina

Downnload...