Rancang Bangun Ulang Mini Brine Cooling Menggunakan R404a Sebagai Refrigeran Primer Dan Campuran Propylene Glycol Dengan Air Sebagai Refrigeran Sekunder

Redesign Mini Brine Cooling Using R404 as Primary Refrigerant and Mixture of Propylene Glycol with Water as a Secondary Refrigerant

Skripsi, 008 / 2018 / PTU
Undergraduate Theses from JBPTPPOLBAN / 2019-01-10 10:34:46
Oleh : Dwiana Aulia A. - 141624009 (dwianaauliaa32@gmail.com)
Dibuat : 2019-01-10, dengan 4 file

Keyword : Performansi Refrigerasi, Mini Brine Cooling, Propylene Glycol, R-404A
Subjek : Refrigeration Performance, Mini Brine Cooling, Propylene Glycol, R-404A

Mesin mini brine cooling merupakan suatu sistem kompresi uap yang menggunakan refrigeran sekunder berupa propylene glycol dengan konsentrasi 15% dan konsentrasi air sebanyak 85% berdasarkan perbandingan konsentrasi massa. Tujuan penggunaan dari refrigeran sekunder ini adalah untuk mengurangi konsumsi energi listrik yang berlebihan selama sistem beroperasi dengan pengkondisian udara dingin pada kabin penyimpanan susu kemasan sebanyak 2 liter. Berdasarkan hasil yang didapatkan pada pengamatan dan pengolahan data, maka diperoleh nilai perbandingan performansi sistem. Nilai COPaktual yang diperoleh menggunakan refrigeran R-404A untuk tugas akhir ini adalah sebesar 1.84 dan nilai COPcarnot yang diperoleh adalah sebesar 4.23 serta nilai efisiensi sebesar 43,49%. Nilai COP sistem tersebut diambil pada menit ke 250 dengan nilai temperatur evaporasi -23,91⁰C dan temperatur kondensasinya 34,86⁰C. Sementara itu nilai rata-rata dari COPaktual dan COPcarnot yang didapat selama keadaan on cycle (beroperasi) yaitu 1,82 dan 4,28 dengan nilai rata-rata efisiensinya sebesar 42,5%. Adapun nilai rata-rata konsumsi daya listrik yang menggunakan R-404A selama proses pengambilan data yaitu sebesar 550 Watt. Selama proses pengambilan data menggunakan refrigeran R-404A, chilling time kabin produk tercapai pada menit ke 250 dengan temperatur yang terukur sebesar 4,1⁰C dan chilling time brine tercapai pada menit ke 50 dengan temperatur terukur sebesar -6⁰C. Sebelum dirancang ulang, COPactual 2.11, efisiensinya sebesar 41.29% COPcarnot 2.13, efisiensi rata-rata 46.8%. Daya listrik yang digunakan sebesar 418 Watt, besarnya energi yang terpakai adalah 0.458 kWh. Dilihat dari data tersebut bahwa sistem setelah dirancang bangun ulang dapat dikatakan berhasil, karna sistem sebelum dirancang bangun ulang pengambilan data secondary refrigerant tidak dalam temperatur yang sama dengan temperatur ambien yaitu 24.2 untuk temperatur ambien sedangkan temperatur awal brine 9.6⁰C. Kata Kunci: Performansi Refrigerasi, Mini Brine Cooling, Propylene Glycol, R-404A.

Deskripsi Alternatif :

The mini brine cooling machine is one of a vapor-compression refrigeration system that using secondary refrigerant such as propylene glycol with a concentration of 15% and water with a concentration of 85% based on mass concentration ratio. The purpose of the use of this secondary refrigerant is to reduce excessive consumption energy while the system operates to conditioned and stored 2 liter of milk. Based on the results from this research and processing the data, we can obtained the comparison value of the system performance. The COPactual value using R-404A refrigerant for this this research is 1.84 and the COPcarnot value is 4.23 and the efficiency value is 43.49%. The COP value of this system is taken in the 250th minute with the evaporation temperature at -23.91⁰C and its condensation temperature at 34.86⁰C. Meanwhile the average value of COPactual and COPcarnot obtained during the on cycle (operating) state are 1.82 and 4.28 with an average efficiency around 42.5%. The average value of electricity consumption using R-404A during the data being taken is around 550 Watts. During the data retrieval process using R-404A refrigerant, the product chilling time is reached in the 250th minutes with measured temperature at 4.1⁰C and the chilling time brine is reached in the 50th minutes with a measured temperature at -6⁰C. Before this system had redesigned, the COPactual was 2.11, the efficiency was 41.29% COPcarnot was 2.13, average efficiency was 46.8%. The electrical power used was 418 Watts, the amount of energy used was 0.458 kWh. Judging from these data that this system after being re-designed can be said to be successful, because before the system being redesigned, the data of secondary refrigerant was not at the same temperature as the ambient temperature at 24.2 while the initial temperature of brine at 9.6⁰C. Keywords: Refrigeration Performance, Mini Brine Cooling, Propylene Glycol, R-404A.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakHelmi Purwanti
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorhelmi.purwanti@polban.ac.id
E-mail CKOhelmi.purwanti@polban.ac.id