Kaji Eksperimental Perbandingan Performansi Antara Refrigeran Sekunder Ethylene GLycol-Air dengan Propylene Glycol-Air Pada Mini Brine Cooling R-404A

Experimental Study of Performance Comparison between Ethylene Glycol-Water and Propylene Glycol-Water as Secondary Refrigerant on Mini Brine cooling R-404A

Skripsi, 013 / 2018 / PTU
Undergraduate Theses from JBPTPPOLBAN / 2019-01-10 11:13:14
Oleh : Fery Ramadhan - 141624015 (feryramadhan25@gmail.com)
Dibuat : 2019-01-10, dengan 4 file

Keyword : Performansi Refrigerasi, Mini Brine Cooling, Propylene Glycol, Ethylene glycol, Refrigeran R-404A
Subjek : Refrigeration Performance, Mini Brine Cooling, Propylene Glycol, R-404A

Mesin mini brine cooling merupakan suatu sistem kompresi uap yang menggunakan compressor berkapasitas 1/7 HP denganmenggunakan refrigerant primer R-404a. Kajian yang dilakukan bertujuan membandingan performansi sistem kompresi uap antara refrigeran sekunderethylene glycol dan air dengan refrigeransekunderpropylene glycol dan air. Makadariitudibuatlahmesinmini brine cooling yang pada evaporatornya di rendam dengan refrigeran sekunder berupa15% propylene glycol dan85%air, selanjutnya refrigeran sekunder di ganti dengan campuran 15% ethylene glycol dan 85% air sebagai media pendinginnya. Perolehan nilai rata-rata dari COPactual dan COPcarnot untuk propylene glycol yang didapat selama keadaan on cycle yaitu 1,82 dan 4,28 dengan nilai rata-rata efisiensinya sebesar 42,50%. Chilling time kabin produk tercapai pada menit ke 205 dengan temperatur sebesar 4,5⁰C dan chilling time pada brine tercapai pada menit ke 165 dengan temperatur sebesar -5⁰C. Dibandingkan dengan nilai rata-rata COPactual dan COPcarnot dari ethylene glycol diketahui sebesar 2,14 dan 4,56 serta nilai rata-rata efisiensinya sebesar 47%. Saat penggunaan ethylene glycol, diketahui kabin produk tercapai pada menit ke 105 dengan temperatur diketahui 4,4⁰C serta chilling time pada brine tercapai pada menit ke 40 sebesar -4,8⁰C. Daya listrik dan energi listrik yang dikonsumsi sistem kompresi uap dengan refrigeran sekunderpropylene glycol diperoleh sebesar 458,45 watt dan 100,94 kWh. Sementara daya listrik dan energi listrik yang menggunakan ethylene glycol adalah 411,47 watt dan 36,667 Kwh. Oleh karena itu refrigeran sekunder ethylene glycol yang digunakan lebih baik performansi sistemnya dibandingkan propylene glycol. Kata Kunci: Performansi Refrigerasi, Mini Brine Cooling, Propylene Glycol, Ethylene glycol, Refrigeran R-404A.

Deskripsi Alternatif :

Mini brine cooling machine is a vapour compression system that using compressor 1/7 HP with primary refrigerant R-404A. This study is to comparing vapour compression system performance between secondary refrigerant ethylene glycol and water than propylene glycol and water. Therefore made a mini brine cooling machine on the evaporator in soak with secondary refrigerant form mixed 15% propylene glycol and 85% water, and then secondary refrigerant change to mixed 15% ethylene glycol and 85% water as cooling media. Earned average value from COPactualand COPcarnotfor propylene glycol gained during on cycle condition is 1,82 and 4,28 with efficiency average value 42,50%. The chilling time on product cabinet is reached on 205 minute with temperature 4,5⁰C and chilling time in brine reached on 165 minute with temperature -5⁰C. Comparing with average value COPactualand COPcarnotfrom ethylene glycol is known 2.14 and 4,56 and efficiency average value 47%. When used ethylene glycol, is known product cabinet reached on 105 minute with temperature 4,4⁰C. The power electricity and power consumption of vapour compression with secondary refrigerant propylene glycol obtained 458,45 Watt and 100,94 kWh. While power electricity and power consumption that using ethylene glycol is 411,47 Watt and 36,667 kWh. Therefore secondary refrigerant ethylene glycol performance that used is better than propylene glycol. Keywords: Refrigeration Performance, Mini Brine Cooling, Propylene Glycol, R-404A.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakHelmi Purwanti
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorhelmi.purwanti@polban.ac.id
E-mail CKOhelmi.purwanti@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: Triaji Pangripto Pramudantoro, S.T., M.Eng.

    Pembimbing 2: A. P. Edi Sukamto, S.T., M.T., Editor: Erlin Arvelina

Download...