Analisa Kandungan Harmonisa Pada Gedung New Sany Rosa Hotel Bandung

Analysis of harmonic content in New Sany Rosa Hotel Bandung Building

Tugas Akhir, 045 / 2018 / TLI
Undergraduate Theses from JBPTPPOLBAN / 2019-05-23 10:38:23
Oleh : Ina Saleha - 151321048 (inasaleha9@gmail.com)
Dibuat : 2019-05-23, dengan 4 file

Keyword : Harmonisa, Kualitas daya dan Alat ukur power analizer
Subjek : Power quality, Harmonic distortion and Power analyzer

Harmonisa merupakan suatu gangguan pada gelombang sinusoidal yang menyebabkan gelombang tersebut terbaca menjadi cacat gelombang. Semakin besar nilai kandungan harmonisa pada suatu sistem tenaga listrik maka semakin menurun pula kualitas daya sistem tenaga listrik tersebut. Pengukuran menggunakan alat ukur power analizer merupakan cara untuk dapat mengetahui nilai kandungan harmonisa sebagai parameter baik atau buruknya kualitas daya pada sistem tenaga listrik di hotel New Sany Rosa Bandung. Setelah mendapatkan hasil pengukuran maka dilakukan analisa dengan metode perbandingan terhadap standar IEEE 591-1992 dan standar IEC 61000-3-2. Hasil pengukuran pada panel LVMDP hotel New Sany Rosa Bandung menunjukan bahwa nilai kandungan harmonisanya memenuhi standar IEEE 591-1992 yaitu THDI di bawah 15% sebesar 10,45%; 8,54% dan 12,78% adapun THDV di bawah 5% sebesar 2,92%; 2,88% dan 3,26%. Nilai tersebut bisa didapatkan karena penggunaan beban beban pada kamar hotel maupun ruangan lainnya seperti lampu LED, lampu TL ballast konvensional maupun pengering pada laundry yang memiliki nilai harmonisa rendah dan memenuhi standar IEC 61000-3-2 bagi beban non linear dengan arus input di bawah 16A. Kata kunci: Harmonisa, Kualitas daya dan Alat ukur power analizer.

Deskripsi Alternatif :

Harmonic distortion is a sinusoidal wave disturbance that caused the fundamental wave be read as a distortion wave. The greater value of the content of harmonics in a power system cause the the decreases of power quality. Using a measuring instrument power analyzer is how to be able to find out the value of the content of harmonics as good or bad the quality parameters of the power system of electric power in the hotel New Sany Rosa Bandung. After getting the results of the measurements then analysis with the method of comparison against the IEEE 5911992 standard and IEC 61000-3-2. The results of measurements on the LVMDP hotel New Sany Rosa Bandung showed that the value of the content of harmonic corresponding to IEEE 591-1992 because THDI under 15% as mention of 10.45%; 8.54% and 12.78% and for THDV are under 5% there are 2.92%; 2.88% and 3.26%. These values can be obtained due to the use of a load burden on hotel rooms or other spaces such as LED lamps, lamp ballasts TL conventional as well as dryer on laundry that has low harmonic distortion values and meet the standards of the IEC 61000-3-2 for non linear load with flow input under 16A. Keywords: Power quality, Harmonic distortion and Power analyzer.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakHelmi Purwanti
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorhelmi.purwanti@polban.ac.id
E-mail CKOhelmi.purwanti@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: Ir. Heri Budi Utomo

    Pembimbing 2: Drs. Kartono Wijayanto., S.T., M.T., Editor: Erlin Arvelina

Download...