Path: Top > Tugas Akhir - D3 > 2017 > Jurusan Teknik Elektro > Program Studi Teknik Listrik > 2019

Rancang Bangun Modul Pengujian Pengaruh Burden CT terhadap Ketelitian Alat Ukur pada Pengukuran Sistem 1Fasa

Design and Development of Testing Module Influence of Burden CT To Measuring Research In Measurement of 1Phase System

Tugas Akhir, 015 / 2019 / TLI
Undergraduate Theses from JBPTPPOLBAN / 2020-03-20 08:56:35
Oleh : Ismiatin Salamah - 161321016 (salamahismiatin1@gmail.com )
Dibuat : 2020-03-20, dengan 4 file

Keyword : Burden, Current Transformer, Measurement, Error.
Subjek : Burden, Trafo Arus, Pengukuran, Error.

Dalam melakukan sebuah pengukuran energi listrik untuk mengubah arus yang besar menjadi arus yang kecil dibutuhkan trafo arus (current transformator). Trafo ini digunakan sebagai proteksi ata juga bisa diigunakan sebagai metering peralatan peralatan listrik yang saling terhubung. Trafo arus (current transformator) ini memiliki burden yang bisa mempengaruhi dalam suatu pengukuran. Pemilihan burden CT yang salah dapat menyebabkan terjadinya eror dalam Pada pengujian ini digunakan beban resistansi dan beberapa trafo yang memiliki burden yang berbeda beda. Untuk mengetahui seberapa besar eror yang disebabkan oleh burden CT , kita harus melakukan beberapa percobaan menggunakan burden CT dengan beban yang berbeda beda. Metode yang digunakan yaitu membuat perancangan yang kemudian dapat dilakukan untuk pengujian guna menghasilkan data yang bisa mengetahui error pada saat pengukuran. Eror yang disebabkan ketika salah memilih Burden CT cukup besar dan melebihi batas standar maksimum kesalahan. Ketika Burden CT < Burden Alat Ukur eror yg terjadi mencapai 46%. Ketika Burden CT = Burden alat Ukur eror yg terjadi hanya 2% dan ketika Burden CT > Burden Alat Ukur eror nya hanya mencapai 1% bahkan 0%.

Deskripsi Alternatif :

In carrying out a measurement of electrical energy to convert large currents into small currents a current transformer is needed. This transformer is used as protection or can also be used as a metering equipment connected to electrical equipment. This current transformer has a burden that can affect in a measurement. Selection of the wrong CT burden can cause errors in this test. Resistance loads and several transformers that have different loads are used. To find out how much error is caused by the CT burden, we have to do some experiments using CT burdens with different loads. The method used is to make a design which can then be carried out for testing in order to produce data that can find errors at the time of measurement. The error caused when incorrectly choosing Burden CT is quite large and exceeds the maximum standard error. When Burden CT Burden the measurement error only reaches 1% or even 0%.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakHelmi Purwanti
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorhelmi.purwanti@polban.ac.id
E-mail CKOhelmi.purwanti@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: Drs. Dwi Asmono, M.Pd.


    Pembimbing 2: Ir. Hari Purnama, M.Eng. , Editor: Muhammad Abdillah Islamy, S.Pd

Download...