Pembuatan dan Pengujian Data Loger Termokopel berbasis Mikrokontroler Arduino Uno secara Portable

Building and Testing Thermocouple Data Logger based on the Arduino Uno Microcontroller in Portable

Tugas Akhir, 072 / 2013 / RTU
Undergraduate Theses from JBPTPPOLBAN / 2017-04-25 15:03:16
Oleh : Jerry Rizky Ramadhan - 101611081 (Jerryramadhan@gmail.com)
Dibuat : 2017-04-25, dengan 4 file

Keyword : Pengukuran, Data Akusisi, Data Logger, Temperatur, Termokopel, Arduino, errors, kehandalan
Subjek : Measurement, Data Acquisition, Data Logger, Arduino, Temeprature, thermocouple errors, reliability

Pengukuran temperatur sangat dibutuhkan terutama pada bidang Refrigerasi dan Tata Udara. Kebutuhan mengumpulkan data menyangkut kebutuhan informasi pengukuran untuk disimpan dan kemudian diproses dan analisa. Untuk menganalisa data dibutuhkan data yang banyak berupa data akusisi. Pengukuran sistem akusisi data untuk temperatur yang digunakan berupa digital yang menggunakan datalogger temperatur komersial. Dalam hal ini penggunaan datalogger temperatur komersial sangat membutuhkan biaya yang cukup mahal, oleh sebab itu pemecahan masalah dalam penggunaan datalogger temperatur berbiaya murah harus ditingkatkan lagi. Dalam hal ini Pembuatan sebuah datalogger termokopel berdasarkan platform Ardurnio. Pembuatan sebuah data logger termokopel membutuhkan beberapa proses tahap pembuatan yaitu perakitan, pemilihan alat, menghubungkan antara komponen serta instalisasi dan upload program pada software Arduino. Pemilihan komponen yang terpenting adalah amplifier AD595 sebagai penguat pada termokopel dan multiplexer ADG407 yang memungkinkan memberi channel 8 termokopel. Setelah itu proses selanjutnya adalah integrasi antara Hardware datalogger temperatur dengan software dan program. Pengujian datalogger termokopel ini dilakukan dengan berupa pengujian akurasi berdasarkan nilai errors dengan Referensi langsung pada Fluke 724 dan Berdasarkan data pengukuran. Dari hasil pengujian datalogger termokopel ini mempunyai errors 10.7 % pada 100C, 5.7 % pada 200C, 3 % pada 300C, 2.9 % pada 400C dan 1.9 % pada 500C. Dan pada pengukuran temperatur di kabin sistem refrigerasi thermoelektik dan pengukuran temperatur di lingkungan Laboratorium Tata Udara dengan channel yang bervariasi error tidak melebihi ±30C sesuai dengan datasheet AD595. Selain itu hasil dari pengujian kehandalan bahwa datalogger termokopel berdasarkan kehandalan dalam mencatat data temperature sebanyak 4369 data, dengan setiap interval 10 detik satu data selama 12 jam dan kehandalan dalam pemakaian baterai 9V selama 1 jam. Kata kunci: Pengukuran, Data Akusisi, Data Logger, Temperatur, Termokopel, Arduino, errors, kehandalan.

Deskripsi Alternatif :

Temperature measurement is necessary, especially in areas of Refrigeration and Air condition. The needs of to collect data concerning the measurement information needs to be stored and then processed and analyzed. To analyze the data takes a lot of data in the form of data acquisition. To analyze the data needs a lot of data in the form of data acquisition. Measurement data acquisition system used for temperature digital a using temperature data logger commercial. In this case the use of temperature dataloggers commercial so requires a significant financial cost. Therefore, solving problems in the use of low-cost data loggers should be increased again. In this case making of a thermocouple dataloggers based Ardurnio platform. Making of a thermocouple dataloggers need several phase of making the assembly process, selection tool, connecting between components as well as the instalisasi and upload programs to Arduino software. Selection of the most important components is the amplifier AD595 as the thermocouple amplifier and multiplexer ADG407 allowing gives 8 channel thermocouples. After the process is most important was the integration between the hardware temperature datalogger with software. Thermocouple datalogger testing was done with testing accuracy errors with reference values based on directly on the Fluke 724 and based on the measurement data. The results of tests thermocouple datalogger has a 10.7% errors at 100C, 5.7% at 200C, 300C 3%, 2.9% and 1.9% at 400C and at 500C. And temperature measurement in the cabin at thermoelektric refrigeration systems and temperature measurements in the environment Air Condition laboratory has channel varied error does not exceeded ± 30C accordance with datasheet AD595. In addition, the results of reliability testing that datalogger thermocouple based on temperature record data reliability in 4369 as the data, with each 10-second intervals during the 12 hours of data and reliability in the use of a 9V battery for 1 hour. Keywords: Measurement, Data Acquisition, Data Logger, Arduino, Temeprature, thermocouple errors, reliability.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakHelmi Purwanti
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorhelmi.purwanti@polban.ac.id
E-mail CKOhelmi.purwanti@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: Drs. Ismail Wellid, M.T.

    Pembimbing 2: Muhammad Arman, S.T., S.Psi., Editor: Erlin Arvelina

Download...