Analisis Variasi Putaran Fan Kondenser Highstage Pada Sistem Refrigerasi Cascade

Analysis Variation Of Rotation Fan Condenser Highstage on System Refrigeration Cascade

Skripsi, 018 / 2018 / PTU
Undergraduate Theses from JBPTPPOLBAN / 2019-01-14 10:21:37
Oleh : Mochammad Faisal Basya - 141624020 (faisalbasya@gmail.com)
Dibuat : 2019-01-14, dengan 4 file

Keyword : Sistem Refrigerasi Cascade, Konsumsi Energi listrik, COP Efisiensi
Subjek : Cascade Refrigeration System, Electric Energy Consumption, COP, Efficiency

Tujuan dari penelitian tugas akhir ini yaitu melakukan uji performansi pada sistem refrigerasi cascade dengan melakukan variasi putaran fan condenser pada sisi highstage. Dengan melakukan variasi tersebut dapat diketahui efisiensi sistem dan juga energi listrik yang dikonsumsi oleh sistem. Metoda yang dilakukan untuk mendapatkan data data yang diinginkan adalah dengan pengambilan data, analisis data lalu membuat kesimpulan. Jumlah variasi yang akan dilakukan sebanyak tiga kali variasi kecepatan fan kondenser highstage pada kondisi 100%, 80% dan 60% dan juga melakukan pengukuran temperatur dan tekanan. Data yang telah diperoleh kemudian diolah untuk mengetahui COPactual,COPCarnot, efisiensi, dan konsumi energi listrik. Hasil dari permormansi dari tiga variasi tersebut adalah pada kondisi putaran fan kondenser highstage 100%, Nilai COPactual yang didapat yaitu 1.63, Nilai COPCarnot yaitu 2.66 sehingga didapat efisiensi sebesar 61.3%. konsumsi listrik yang dihasilkan oleh sistem sebesar 386.63 kWh/bulan. pada kondisi 80%, Nilai COPactual 1.5, Nilai COPCarnot 2.72 sehingga efisiensi sebesar 57.1%. konsumsi listrik yang dihasilkan sebesar 376.8 kWh/bulan. pada kondisi 60%, Nilai COPactual 1.51, Nilai COPCarnot 2.66 sehingga efisiensi sebesar 56.85%. konsumsi listrik yang dihasilkan 398.8 kWh/bulan. Kta kunci: Sistem Refrigerasi Cascade, Konsumsi Energi listrik, COP Efisiensi.

Deskripsi Alternatif :

The purpose of this final task research is to perform performance test on the cascade refrigeration system by varying the rotation of the fan condenser on the highstage side. By doing these variations can be known system efficiency and also electrical energy consumed by the system. The method used to get the data of the desired data is by taking data, data analysis and then make conclusion. The amount of variation that will be done three times variation of highstage condenser fan speed at 100%, 80% and 60% condition and also to do temperature and pressure measurement. The data have been obtained then processed to know COPactual, COPCarnot, efficiency, and consume electrical energy. The result of permeability of three variations is on condenser fan condenser condition 100% highstage, COPactual value obtained that is 1.63, COPCarnot value is 2.66 so that obtained efficiency of 61.3%. electricity consumption generated by the system of 386.63 kWh / month. at 80% condition, COPactual value 1.5, COPCarnot value 2.72 so efficiency is 57.1%. electricity consumption is 376.8 kWh / month. at 60%, COPactual value 1.51, COPCarnot 2.66 value so that efficiency is 56.85%. electricity consumption generated 398.8 kWh / month. Keywords: Cascade Refrigeration System, Electric Energy Consumption, COP, Efficiency.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakHelmi Purwanti
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorhelmi.purwanti@polban.ac.id
E-mail CKOhelmi.purwanti@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: Triaji Pangripto Pramudantoro, S.T., M.Eng.

    Pembimbing 2: Ir. Sumeru, M.T., Ph.D., Editor: Erlin Arvelina

Download...