Kaji Eksperimental Performansi Mini Brine Cooling Menggunakan R404A Sebagai Primary Refrigerant dan Ethylene Glycol Sebagai Secondary Refrigerant

Experimental Study of Mini Brine Cooling Performance Using R404A as Primary Refrigerant and Ethylene Glycol as Secondary Refrigerant

Skripsi, 019 / 2018 / PTU
Undergraduate Theses from JBPTPPOLBAN / 2019-01-14 10:28:12
Oleh : Mochammad Firmansyah - 141624021 (moch.firman19@gmail.com)
Dibuat : 2019-01-14, dengan 4 file

Keyword : Performansi Refrigerasi, Mini Brine Cooling, Ethylene Glycol, Refrigeran R-404A, Produk Susu
Subjek : Refrigeration Performance, Mini Brine Cooling, Propylene Glycol, Refrigerant R-404A, Refrigerant R-22, Milk

Mesin mini brine cooling merupakan suatu sistem kompresi uap yang menggunakan refrigeran sekunder. Penggunaan dari refrigeran sekunder ini adalah untuk mengoptimalkan konsumsi energi listrik yang berlebihan selama sistem beroperasi. Kajian yang dilakukan bertujuan untuk mengkaji performansi sistem refrigerasi kompresi uap menggunakan R-404A sebagai primary refrigerant dan ethylene glycol dengan konsentrasi 15% dan konsentrasi air sebanyak 85% berdasarkan konsentrasi massa sebagai secondary refrigerant. Metoda yang dilakukan adalah dengan menggunakan kompresor dengan daya input 2/5 HP. Produk yang didinginkan berupa susu kemasan dengan temperatur kabin diatur 4,5 oC dan kabin brine -4,5oC. Temperatur evaporasi dan kondensasi didapat masing-masing -13,9oC dan 63,6oC. Perolehan nilai rata-rata COPactual dan COPcarnot selama keadaan on cycle yaitu 2,15 dan 4,57. Nilai rata-rata efisiensinya sebesar 47,01%. Chilling time kabin produk dan brine masing-masing tercapai pada menit ke-40 dan 105. Energi listrik yang dikonsumsi sebesar 36,67 kWh. Kata Kunci: Performansi Refrigerasi, Mini Brine Cooling, Ethylene Glycol, Refrigeran R-404A, Produk Susu.

Deskripsi Alternatif :

Mini brine cooling machine is a vapor compression system that use secondary refrigerant. The use of these secondary refrigerants is to optimize the excessive consumption of electrical energy during the operating system. The study aimed to assess the performance of steam compression refrigeration system using R-404A as primary refrigerant and ethylene glycol with concentration of 15% and water concentration of 85% based on mass concentration as secondary refrigerant. The method used is to use a compressor with an input power of 2/5 HP. The product is cooled in the form of milk packaging with product cabin temperature set 4,5oC and brine cabin temperature set -4,5oC . Evaporation and condensation temperature were obtain at -13,9oC. The average values of COPactual and COPCarnot during the on cycle are 2,15 and 4,57. The average value of efficiency is 47,01%. Chilling time of product cabin and brine respectively reached at minute 40 and 105. Electric energy consumed equal to 36,67 kWh. Keywords: Refrigeration Performance, Mini Brine Cooling, Propylene Glycol, Refrigerant R-404A, Refrigerant R-22, Milk.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakHelmi Purwanti
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorhelmi.purwanti@polban.ac.id
E-mail CKOhelmi.purwanti@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: Triaji Pangripto Pramudantoro, S.T., M.Eng.

    Pembimbing 2: A. P. Edi Sukamto, S.T., M.T., Editor: Erlin Arvelina

Download...