Perancangan Sistem Proteksi Kebakaran Pada Gedung Student Center Politeknik Negeri Indramayu Dengan Memanfaatkan Air Hujan

Design of a Fire Protection System in the Student Center Building of the Indramayu State Polytechnic by Utilizing Rainwater

Tugas Akhir, 014 / 2021 / KGE
Undergraduate Theses from JBPTPPOLBAN / 2022-06-13 09:47:16
Oleh : Nandi Lutfi Rahmi - 181111021 (nandi.lutfi.tkgd18@polban.ac.id )
Dibuat : 2022-06-13, dengan 4 file

Keyword : Protection system, hydrant, sprinkler, and rain water.
Subjek : Sistem proteksi, hidran, sprinkler, dan air hujan.

Politeknik Negeri Indramayu berawal dari adanya rencana pemerintah untuk meningkatkan jumlah Pendidikan Vokasi . Student Center Politeknik Negeri Indramayu merupakan gedung dengan tinggi 8 (delapan) lantai dan luas bangunan 6550 m2. Bangunan tersebut terdiri dari kumpulan ruangan-ruangan kelas, ruang pelayanan akademik, ruang dosen, perpustakaan, auditorium, dan semi basement sebagai ruang parkir kendaraan. Pada gedung student center ini belum tersedia instalasi sistem proteksi kebakaran, padahal sistem proteksi pemadam kebakaran sangat penting untuk mencegah merambatnya kebakaran dan mengamankan aset-aset. Menurut Peraturan Pemerintah PP Nomor 16 Tahun 2021 Pasal 30 Ayat 1 Setiap Bangunan Gedung harus dilindungi sistem proteksi bahaya kebakaran, gedung Student Center Politeknik Negeri Indramayu termasuk pada kelas 9b (bangunan pertemuan), dimana gedung Student Center Politeknik Negeri Indramayu seharusnya memiliki sistem proteksi kebakaran aktif maupun pasif. Namun kenyataanya Politeknik Negeri Indramayu belum dilengkapi dengan sistem proteksi kebakaran aktif maupun pasif. Maka penulis tertarik untuk merancang sistem proteksi kebakaran aktif dengan memanfaatkan air hujan sebagai sumber airnya. Hasil dari perancangan ini berupa rancangan instalasi hidran gedung dan sprinkler. Instalasi hidran 11 titik dan 1 hidran siamase. Sistem sprinkler ini menggunakan tipe pendent dengan suhu 68oC dan berjumlah 310 buah. Kebutuhan air untuk sistem hidran dan sprinkler sebesar 2357 m3. Sedangkan dari hasil pemanen air hujan sebesar 801,66 m3/tahun. Maka kekurangan air untuk sistem proteksi kebakaran aktif sebesar 1556 m3 disuplai dari PDAM.

Deskripsi Alternatif :

Indramayu State Polytechnic began with the government plans to increase the number of Vocational Education. The Student Center is a building with total of 8 (eight) floors and a width of 6550 m2. The building consists of a collection of classrooms, academic service rooms, lecturer rooms, library, auditorium, and semi-basement as vehicle parking space. In this student center building, there are not any fire protection system installation, even though this system is very important to prevent the spread of fires and secure assets. According to government regulation number 16 of 2021 article 30 paragraph 1, every building must be protected by a fire hazard protection system, class 9b (meeting building), where the Student Center building of the Indramayu State Polytechnic should have an active or passive fire protection system”. However, in reality there has not been equipped with either active or passive fire protection system. So the author is interested in designing an active fire protection system by utilizing rainwater as a source. The result of this design is building hydrants and sprinkler installations design. Installations of 11 point hydrants and 1 twin hydrant. This sprinkler system uses a pendent type with a temperature of 68oC and totals 310 pieces. The water requirement for the hydrants and sprinkler system is 2357 m3. Meanwhile, from the rainwater harvester, it is 801.66 m3/year. So the lack of water for the active fire protection system of 1556 m3 is supplied from the PDAM.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakErlin Arvelina
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorerlin.arvelina@polban.ac.id
E-mail CKOerlin.arvelina@polban.ac.id