Path: Top > Tugas Akhir - D3 > 2017 > Jurusan Teknik Refrigerasi & Tata Udara > Program Studi Teknik Pendingin & Tata Udara > 2019
Analisis Perbandingan Alat Ekspansi TXV dan Pipa Kapiler Low Stage pada Performansi Sistem Refrigerasi Cascade
Comparison Analysis of Expansion Devices Using TXV and Capillary Tube Low Stage of Cascade Refrigeration System Performance
Tugas Akhir, 023 / 2019 / RTUUndergraduate Theses from JBPTPPOLBAN / 2020-04-02 21:42:57
Oleh : Nur Arifin - 161611025 (arifin.nur1996@gmail.com)
Dibuat : 2020-04-02, dengan 4 file
Keyword : Sistem Refrigerasi Cascade, COP, Efisiensi, Penggunaan Energi Listrik
Subjek : Cascade Refrigeration System, COP, Efficiency, Electric Energy Consumption
Sistem refrigerasi cascade merupakan gabungan dari dua sistem refrigerasi tunggal, yaitu sistem high stage dan sistem low stage. Pada hal ini, perbandingan performansi dilakukan pada sistem refrigerasi cascade dengan melakukan variasi alat ekspansi TXV dan pipa kapiler pada sistem low stage. Dengan melakukan variasi tersebut, performansi sistem dan juga penggunaan energi listrik yang digunakan oleh sistem dapat diketahui. Hasil dari variasi alat ekspansi tersebut adalah pada sistem dengan menggunakan alat ekspansi TXV, nilai COPaktual yang didapat, yaitu 1,24, nilai COPCarnot, yaitu 2,57 sehingga didapat efisiensi sebesar 48%, dan penggunaan energi listrik yang dihasilkan oleh sistem sebesar 1,42 kWh. Sedangkan, sistem dengan alat ekspansi pipa kapiler, nilai COPaktual yang didapat, yaitu 1,01, nilai COPCarnot, yaitu 2,48 sehingga didapat efisiensi sebesar 41%, dan penggunaan energi listrik yang dihasilkan sebesar 1,11 kWh. Kata Kunci: Sistem Refrigerasi Cascade, COP, Efisiensi, Penggunaan Energi Listrik.
Deskripsi Alternatif :Cascade refrigeration system is a combination of two single refrigeration systems, namely a high stage system and a low stage system. In this case, a performance comparison is performed on the cascade refrigeration system by varying the TXV expansion device and capillary pipes in the low stage system. By doing these variations, the system performance and also the use of electrical energy used by the system can be known. The results of the variation of the expansion device is the system using the TXV expansion tool, the COPactual value obtained, which is 1.24, the COPCarnot value, which is 2.57 so that an efficiency of 48% is obtained, and the use of electrical energy generated by the system is 1.42 kWh. Meanwhile, the system with capillary pipe expansion tool, the COPactual value obtained, which is 1.01, the COPCarnot value, which is 2.48 so that the efficiency obtained by 41%, and the use of electricity generated by the system is 1.11 kWh. Keywords: Cascade Refrigeration System, COP, Efficiency, Electric Energy Consumption.
Beri Komentar ?#(0) | Bookmark
Properti | Nilai Properti |
---|---|
ID Publisher | JBPTPPOLBAN |
Organisasi | |
Nama Kontak | Helmi Purwanti |
Alamat | Jl. Trsn. Gegerkalong Hilir Ds. Ciwaruga |
Kota | Bandung |
Daerah | Jawa Barat |
Negara | Indonesia |
Telepon | 022 201 3789 ext. 168, 169, 239 |
Fax | 022 201 3889 |
E-mail Administrator | helmi.purwanti@polban.ac.id |
E-mail CKO | helmi.purwanti@polban.ac.id |
Print ...
Kontributor...
- Pembimbing 1: A. P. Edi Sukamto, S.T., M.T.
Pembimbing 2: Tandi Sutandi, S.ST., M.T., Editor: Erlin Arvelina
Download...
File : KELENGKAPAN TA - 161611025.pdf
(2472265 bytes)
File : BAB 1 - 161611025.pdf
(453231 bytes)
File : BAB 2 - 161611025.pdf
(3313341 bytes)
File : BAB 5 - 161611025.pdf
(272903 bytes)