Trafo arus yaitu suatu peralatan yang dapat memperkecil arus besar menjadi arus kecil yang dipergunakan dalam pemanfaatan pengukuran dan proteksi. Tidak hanya spesifikasi rasio trafo arus yang perlu diperhatikan, namun perhitungan burden pun harus diperhatikan agar CT dapat berfungsi dengan baik sesuai yang dibutuhkannya. Trafo arus pengukuran memiliki ketelitian tinggi pada daerah kerjanya yaitu 5% sampai 120% arus nominalnya, namun dalam kenyataannya yang paling baik adalah kondisi saat dibebani 100% dan 120% karena ketelitiannya sesuai dengan kelas ketelitian trafo yang digunakan. Dalam tugas akhir ini akan dibahas mengenai pengaruh pembebanan pada sisi sekunder trafo yang akan mengakibatkan ketelitian pada alat ukur atau metering. Studi yang dilakukan meliputi pengujian, perhitungan daya yang terukur, daya yang digunakan, dan error. Pada pengujian ini menggunakan CT pengukuran tiga buah yang memiliki kapasitas burden yang berbeda, guna mengetahui pengaruh burden pada suatu sistem rangkaian. Semakin kecil error atau kesalahannya, maka semakin teliti alat tersebut. Sesuai standar SPLN No.55 Tahun 1990 bahwa error masih diizinkan apabila hasilnya tidak melebihi ±5% Studi yang dilakukan bahwa CT yang memiliki burden lebih besar dari burden beban merupakan pemilihan yang tepat sesuai pembebanannya.

Deskripsi Alternatif :

Current transformer is a device that can reduce large currents into small currents used in the use of measurements and protection. Not only the current transformer ratio specifications that need to be considered, but the burden calculation must also be considered so that CT can function properly as needed. The measurement current transformer has a high accuracy in the working area of 5% to 120% of the nominal current, but in reality the best condition is when it is loaded 100% and 120% because the accuracy is in accordance with the precision class of the transformer used. In this final project will be discussed about the influence of loading on the transformer secondary side which will result in accuracy in measuring or metering tools. Studies conducted include testing, measured power calculation, power used, and error. In this test using CT measurements of three pieces that have different burden capacities, in order to determine the effect of the burden on a circuit system. The smaller the error or error, the more thorough the tool. In accordance with SPLN standard No.55 of 1990 that errors are still permitted if the results do not exceed ± 5%. Studies conducted that CT which has a greater burden than the burden of the burden is the right choice according to its loading.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakHelmi Purwanti
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorhelmi.purwanti@polban.ac.id
E-mail CKOhelmi.purwanti@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: Drs. Dwi Asmono, M.Pd.


    Pembimbing 1: Ir. Hari Purnama, M.Eng., Editor: Muhammad Abdillah Islamy, S.Pd

Download...