Path: Top > Karya Tulis Ilmiah Tenaga Pendidik POLBAN di Terbitan Institusi Lain > Sofian Yahya

Rancang Bangun Protipe Perangkat Pengukuran dan Monitoring Besaran Listrik Menggunakan PLC Berbasis LabVIEW

Design of Prototype Measurement Device and Monitoring Electrical Quantities Using PLC based LabVIEW

JTET Vol. 2 No. 3 Desember 2013: 121-128. ISSN 2252-4908
Journal from JBPTPPOLBAN / 2014-05-13 08:25:36
Oleh : Sofian Yahya; Sarjono Wahyu Jadmiko; Dedi Nono Suharno (sofianyahya@polban.ac.id)
Dibuat : 2014-05-12, dengan 1 file

Keyword : Synchronous Generator, LabVIEW, Power Meter, Programmable Logic Controller, Protocol Modbus

Untuk proses monitoring besaran listrik dari suatu pembangkit tenaga listrik diperlukan suatu perangkat antar muka elektronik. Perangkat ini merupakan bagian dari sistem SCADA (Supervisory Control and Data Acquisition). SCADA pada umumnya terdiri dari Master Terminal Unit (MTU) yang memonitor dan mengendalikan dari jarak jauh, MTU mengendalikan Remote Terminal Unit (RTU) secara otomatis. Data yang ada di MTU kemudian direpresentasikan dengan Human Machine Interfaces(HMI). Tulisan ini menyajikan rancang bangun protipe monitoring dan pengukuran besaran listrik dari sebuah generator sinkron menggunakan PLC berbasis LabVIEW. Protipe alat monitoring dan pengu-kuran ini terdiri dari Power Meter SPM-8, Serial Communication Unit (SCU) 41-V1, PLC Omron tipe CJ2M, dan perangkat lunak LabVIEW. Akuisisi data dari Power Meter dilakukan melalui SCU yang di program oleh perangkat lunak CX-Protocol (protocol Modbus), sedangkan eksekusi sequence read/write data dari power meter dilakukan oleh instruksi PMCR yang diprogram dengan perangkat lunak CX-programmer. Untuk menampilkan besaran listrik yang terukur digunakan LabVIEW, data diakses dari memori data PLC. Tujuan dari penelitan merancang protipe alat yang mampu memonitor dan mengukur besaran listrik secara realtime dengan LabVIEW dengan error ± 5% dari nilai yang terukur di Power Meter. Berdasarkan hasil pengujian error pengukuran rata-rata di LabVIEW lebih tinggi 1,24%, sehingga alat yang dibuat sudah sesuai dengan spesifikasi yang ingin dicapai.

Deskripsi Alternatif :

An electronic interface is required to monitor as well as to measure electric parameters in a power generator. This hardware is part of SCADA (Supervisory Control and Data Acquisition) system. SCADA generally consists of Master Terminal Unit (MTU) used to monitor and control remotely and Remote Terminal Unit (RTU) controlled by MTU. Data in MTU is represented by Human Machine Interfaces (HMI. This paper presents prototype design to monitor and to measure electric parameters in a synchronized power generator by means of LabVIEW based PLC. This monitoring and measuring device prototype comprises Power Meter SPM-8, Serial Communication Unit (SCU) 41-V1, PLC Omron tipe CJ2M, and LabVIEW software. Data acquisition from Power Meter is performed via SCU programmed by CX- Protocol (protocol Modbus), while sequence read/write data executed from power meter by PMCR instruction programmed by CX-programmer. LabVIEW is used to display measured electric parameters, data is accessed from PLC data memory. The purposes of this research is to be able to monitor and to measure electric parameters real time using LabVIEW with ± 5% error from the measured value in Power Meter. Based on error evaluation, average measurement in LabVIEW is 1.24% higher. This concludes that the device made meets the specification to achieve.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakErlin Arvelina
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorerlin.arvelina@polban.ac.id
E-mail CKOerlin.arvelina@polban.ac.id