Analisis Pengaruh Descaling Kondenser Terhadap Efisiensi Three Stage Water Cooled Chiller Trane Tipe CVHG 1100TR Dengan Refrigeran R123 Di Bandung Electronic Center (BEC)

Analysis of Condenser Descaling Effects to Efficiency of Three Stage Trane's Water Cooled Chiller Type CVHG 1100TR with Refrigerant R123 on Bandung Electronic Center (BEC)

Tugas Akhir, 025 / 2018 / RTU
Undergraduate Theses from JBPTPPOLBAN / 2019-01-21 14:05:46
Oleh : Sulma Mahardiani - 151611028 (smahardiani@gmail.com)
Dibuat : 2019-01-21, dengan 4 file

Keyword : Watercooled chiller, efisiensi, scaling, biaya operasional
Subjek : water cooled chiller, efficiency, scaling, operational cost

Pada laporan ini dilakukan analisis pengaruh scaling kondenser terhadap efisiensi water cooled chiller. Data untuk penelitian diambil dari water cooled chiller tipe CVHG 1100TR di Bandung Electronic Center (BEC), karena satu dari tiga unit chiller memiliki kW/TR yang tinggi, maka dilakukan scaling kondenser. Tujuan penelitian adalah untuk mengetahui pengaruh scaling terhadap efisiensi sistem dan menghitung biaya operasionalnya. Efisiensi dapat dikatakan baik pada sebuah sistem chiller yaitu dengan melihat parameter-parameter seperti ΔT evaporator dan kondenser, approach, konsumsi daya, kapasitas pendinginan, efisiensi dan COP. Pengamatan utama yaitu kW/TR atau efisiensi, karena hal yang paling penting dari sistem chiller di bangunan komersial adalah biaya operasionalnya. Setelah dilakukan penelitian, kW/TR setelah dilakukan scaling mengalami penurunan dari 0.53 kW/TR menjadi 0.43 kW/TR, sehingga biaya operasionalnya pun menurun dari Rp. 263,088,000 menjadi Rp. 216,720,000 perbulan, sehingga sistem dapat melakukan penghematan hingga Rp. 50,000,000 perbulan. Efisiensi refrigerasi sebelum dan sesudah scaling dapat dikatakan baik karena mencapai nilai 70%. Kata kunci: Watercooled chiller, efisiensi, scaling, biaya operasional.

Deskripsi Alternatif :

In this report, the analysis of the effect of condenser scaling on the efficiency of water cooled chiller. The data for research is taken from water cooled chiller type CVHG 1100TR at Bandung Electronic Center (BEC), because one of three chiller units has a high kW / TR, then a condenser scaling is performed. The purpose of this research is to know the effect of scaling on system efficiency and calculate its operational cost. Efficiency can be said good on a chiller system by looking at parameters such as ΔT evaporator and condenser, approach, power consumption, cooling capacity, efficiency and COP. The main observation is kW / TR or efficiency, because the most important thing of a chiller system in a commercial building is its operational costs. After the research, kW / TR after the scaling has decreased from 0.53 kW / TR to 0.43 kW / TR, so that the operational cost also decreased from Rp. 263,088,000 to Rp. 216,720,000 per month, so the system can save up to Rp. 50,000,000 per month. The efficiency of refrigeration before and after scaling can be said to be good because it reaches 70%. Keywords: water cooled chiller, efficiency, scaling, operational cost.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakHelmi Purwanti
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorhelmi.purwanti@polban.ac.id
E-mail CKOhelmi.purwanti@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: Dr. Ir. Andriyanto Setyawan, M.T.

    Pembimbing 2: Triaji Pangripto Pramudantoro, S.T., M.Eng., Editor: Erlin Arvelina

Download...