Pengaruh Harmonisa Dan Faktor Daya Terhadap Pengukuran KwH Meter Satu Fasa Dengan Beban Instalasi Daya

The Influence of Harmonic and Power Factor Value to Single Phase KwH Meter Measurement of Power Installation Load

Tugas Akhir, 061 / 2018 / TLI
Undergraduate Theses from JBPTPPOLBAN / 2019-05-29 14:27:48
Oleh : Zaelani - 151321064 (zaelani990@yahoo.com)
Dibuat : 2019-05-29, dengan 4 file

Keyword : kWh meter, Akurasi, Harmonisa, Gelombang Sinus, Kualitas Daya, Power Quality Analyzer, Faktor Daya, Kapasitor
Subjek : kWh meter, accuracy, Distortion, sine wave, Power Quality, Power Quality Analyzer, Power Factor, Capacitor

Sebagai alat untuk menghitung dan mengukur daya aktif yang terpakai, sudah seharusnya kWh meter mempunyai akurasi yang tinggi dan tidak ada penyimpangan dalam pengukurannya. Tetapi karena semakin banyaknya beban non-linier yang menyebabkan adanya fenomena harmonisa, keakuratan dari kWh meterpun diragukan. Bukan tanpa sebab, karena input dari sebuah kWh meter yang akurat adalah arus dan tegangan yang mempunyai gelombang sinus murni. Fenomena harmonisa menyebabkan gelombang sinus itu cacat dan dikhawatirkan menyebabkan penyimpangan pengukuran pada kWh meter yang selanjutnya akan menyebabkan salah satu pihak dirugikan. Metode analisis yang digunakan adalah dengan cara mengukur beban berharmonisa menggunakan Power Quality Analyzer, kemudian pada kWh meter dapat dilihat perbedaan antara beban berharmonisa dan beban yang tidak mempunyai harmonisa. Setelah dilakukan pengujian, didapat bahwa harmonisa membuat putaran piringan kWh meter berputar lebih lambat dan membuat kedipan kwh digital lebih lambat. Dengan error mencapai 16 %, selisih energi yang terpakai dan terukur mencapai 7 Wh. Sehingga pihak penyalur pun dirugikan. Pemasangan kapasitor 6µF secara paralel pada beban yang mempunyai faktor daya 0,8 membuat faktor daya meningkat menjadi 0,99 dan membuat THDI naik 7% dari semula sebelum dipasang kapasitor. Pemasangan kapasitor juga mengurangi error pembacaan kWh meter sebesar 3%. Kata Kunci: kWh meter, Akurasi, Harmonisa, Gelombang Sinus, Kualitas Daya, Power Quality Analyzer, Faktor Daya, Kapasitor.

Deskripsi Alternatif :

Abstrak English: As a tool for counting and measuring active power is used, it should have meters kWh high accuracy and no deviations in measurement. But because of the growing number of non-linear load that causes the existence of the phenomenon of harmonics, doubt the accuracy of kWh meter. Not without reason, because the input from a kWh meters are accurate is the current and voltage have a pure sine wave. Distortion phenomenon caused the sine wave was flawed and it is feared to cause measurement deviations at kWh meters that would lead to one of the parties aggrieved. Methods of analysis used is with how to measure harmonics load using Power Quality Analyzer, then on the kWh meter can be seen the difference between load and harmonic load who have no distortion. With an error of 16%, the difference in energy used and measured reaches 7 Wh. So that the distributor is harmed. Installing a 6μF capacitor in parallel on a load that has a power factor of 0.8 makes the power factor increase to 0.99 and makes THDI up 7% from the previous one before the capacitor is installed. Installing the capacitor also reduces the kWh meter reading error by 3%. Keywords: kWh meter, accuracy, Distortion, sine wave, Power Quality, Power Quality Analyzer, Power Factor, Capacitor.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakHelmi Purwanti
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorhelmi.purwanti@polban.ac.id
E-mail CKOhelmi.purwanti@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: Drs. Kartono Wijayanto., S.T., M.T.

    Pembimbing 2: Ir. Hari Purnama, M.Eng., Editor: Erlin Arvelina

Download...