Analisis Dampak Harmonisa Terhadap Kinerja Transformator Distribusi 400kva Politeknik Negeri Bandung

Analysis Of The Impact Of Harmonics On The Performance Of 400kva Distribution Transformer In Bandung State Polytechnic

Tugas Akhir, 030 / 2019 / TLI
Undergraduate Theses from JBPTPPOLBAN / 2020-03-23 11:10:40
Oleh : Zaky Rizki Rijaldi - 161321032 (zaky.rizki.tlis16@polban.ac.id )
Dibuat : 2020-03-23, dengan 4 file

Keyword : Nonlinear loads, harmonic, transformer losses, power analyzer, passive filter.
Subjek : Beban nonlinear, Harmonisa, rugi-rugi transformator, alat ukur power analyzer, dan filter pasif.

Beban nonlinear dirancang untuk dapat mengefisienkan dan menghemat penggunaan energi listrik. Akan tetapi disisi lain, penggunaan dari komponen elektronik ini juga menyebabkan gangguan berupa distorsi sinyal arus dan tegangan yang mengalir kembali ke sistem ditribusi listrik. Salah satu peralatan dalam sistem distribusi listrik adalah transformator. Pengaruh harmonisa pada transformator adalah bertambahnya rugi-rugi beban, rugi tembaga, dan rugi Eddy-current. Metoda dalam penelitian ini adalah dengan cara pengukuran nilai kandung harmonisa pada panel LVMDP transformator 400kVA Politeknik Negeri Bandung menggunakan power analyzer dan simulasi filter pasif single tuned menggunakan aplikasi Simulink Matlab untuk mereduksi harmonisa. Hasil pengukuran pada panel LVMDP Politeknik Negeri Bandung menunjukan bahwa nilai kandungan harmonisa arusnya melebihi standar 8% dengan nilai THDi nya yaitu 11,73%, 14,48%, dan 10,55%. Sedangkan untuk nilai kandungan harmonisa tegangannya sesuai dengan standar 8% dengan nilai THDv nya adalah 2,41%, 2,47% dan 2,40%. Maka untuk kandungan nilai harmonisa arus yang melebihi standar, digunakan filter pasif single tunned untuk mereduksi harmonisa dalam bentuk simulasi. Hasil simulasi setelah dipasang filter pasif, nilai kandungan THDi menurun menjadi .0,59%, 0,76%, dan 0,54%.

Deskripsi Alternatif :

Nonlinear load is designed to be efficient and to save the use of electrical energy. But on the other hand, the use of these electronic components also causes interference in the form of distortion of current and voltage signals that flow back to the electricity distribution system. One of the equipment in the electricity distribution system is the transformer. The harmonic effect on the transformer is the increased of load losses, copper losses and Eddy-current losses. The method used on this study is by measuring harmonic value of the 400kVA transformer LVMDP panel. Polban uses a power analyzer and a single tuned passive filter simulation use the Simulink MAtlab application to reduce harmonics. The results on the panel Polban LVMDP shows that the current value of the harmonic content exceeding 8% of the standard with THDi value of 11.73%, 14.48%, and 10.5%. For the value of the harmonic content of the voltage according to the 8% value standard with the THDv value are 2.41%, 2.47% and 2.40%. Hence the current value of harmonic content that exceeds standard, a single passive tuned filters are used to reduce harmonics in the form of simulations. The THDi content value decreases to 0.59%, 0.76% and 0.54% after the simulation using the passive filter that installed.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakHelmi Purwanti
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorhelmi.purwanti@polban.ac.id
E-mail CKOhelmi.purwanti@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: Ir. Heri Budi Utomo


    Pembimbing 2: Ir. Dedi Nono Suharno, M.T. , Editor: Muhammad Abdillah Islamy, S.Pd

Download...