Pengaruh Jumlah Plat terhadap Nilai Efektivitas pada Heat Exchanger Kapasitas 2 MW Reaktor Triga 2000 Bandung
The Effect of the Number of Plates on the Value of Effectiveness in the 2 MW Capacity Heat Exchanger for the Triga 2000 Reaktor in Bandung
Skripsi, 004 / 2023 / TPTLUndergraduate Theses from JBPTPPOLBAN / 2024-03-19 14:35:17
Oleh : 181724026 - Shella Fajri Zahra (shella.fajri.tptl18@polban.ac.id)
Dibuat : 2024-03-19, dengan 4 file
Keyword : Reaktor Triga, Plate Heat Exchanger, LMTD, NTU
Subjek : Triga Reactor, Plate Heat Exchanger, LMTD, NTU
Alat penukar panas yang berada di PSTNT Batan adalah heat exchanger tipe plat yang menggunakan pelat logam untuk mentransfer panas antara dua fluida. Heat exchanger ini bertugas mendinginkan fluida dari pompa primer yang diambil dari air tangki dari reaktor dengan fluida yang ada dalam pompa sekunder. Heat exchanger tipe ini dipisahkan oleh gasket untuk mengarahkan fluida agar mengalir dalam arah berlawanan. Penelitian ini bertujuan untuk membuat perancangan heat exchanger dengan kapasitas 2MW yang akan mempertimbangkan efektivitas alat penukar kalor sehingga tidak akan menimbulkan kerugian sistem. Perancangan dilakukan dengan menambah jumlah plat dalam heat exchanger dengan laju alir yang maksimal. Penambahan jumlah plat akan mempengaruhi luasan dinding, yang dimana di luasan plat terjadi kontak perpindahan panas, akan tetapi perlu dipertimbangkan agar aliran fluida memiliki hambatan yang tidak begitu besar. Analisa alat penukar kalor pelat ini mengunakan Metode LTMD dan NTU-efektifitas, dimana hasil dari LTMD didapat perbedaan suhu rata-rata antara air panas dan air dingin sebesar 4,214°C. Besarnya nilai efektivitas penukar kalor pada pada saat reaktor beroperasi 2000 kWatt mempunyai nilai rata-rata 0,557 dengan penambahan jumlah plat sebanyak 76 plat. Dan nilai rata-rata laju perpindahan panas total Ì sebesar 775.226 kWatt. Kata Kunci: Reaktor Triga, Plate Heat Exchanger, LMTD, NTU.
Deskripsi Alternatif :The heat exchanger in the Batan PSTNT is a plate type heat exchanger that uses metal plates to transfer heat between two fluids. This heat exchanger is in charge of cooling the fluid from the primary pump which is taken from tank water from the reactor with the fluid in the secondary pump. This type of heat exchanger is separated by a gasket to direct the fluid to flow in the opposite direction. This study aims to design a heat exchanger with a capacity of 2MW which will consider the effectiveness of the heat exchanger so that it will not cause system losses. The design is done by increasing the number of plates in the heat exchanger with the maximum flow rate. Increasing the number of plates will affect the wall area, in which the plate area is in contact with heat transfer, but it needs to be considered so that the fluid flow has not so great a resistance. Analysis of this plate heat exchanger uses the LTMD and NTU-effectiveness methods, where the results from LTMD show that the average temperature difference between hot water and cold water is 4.214°C. The value of the effectiveness of the heat exchanger when the reactor is operating at 2000 kWat has an average value of 0.557 with the addition of 76 plates. And the average value of the total heat transfer rate Ì is 775,226 kWatt. Keywords: Triga Reactor, Plate Heat Exchanger, LMTD, NTU.
Beri Komentar ?#(0) | Bookmark
Properti | Nilai Properti |
---|---|
ID Publisher | JBPTPPOLBAN |
Organisasi | |
Nama Kontak | Erlin Arvelina |
Alamat | Jl. Trsn. Gegerkalong Hilir Ds. Ciwaruga |
Kota | Bandung |
Daerah | Jawa Barat |
Negara | Indonesia |
Telepon | 022 201 3789 ext. 168, 169, 239 |
Fax | 022 201 3889 |
E-mail Administrator | erlin.arvelina@polban.ac.id |
E-mail CKO | erlin.arvelina@polban.ac.id |
Print ...
Kontributor...
- Pembimbing 1: Dr. Ignatius Riyadi Mardiyanto, M.T.
Pembimbing 2: Dra. Tina Mulya Gantina, M.T., Editor: Erlin Arvelina
Download...
File : KELENGKAPAN SKRIPSI - 181724026.pdf
(1103690 bytes)
File : BAB 1 - 181724026.pdf
(198822 bytes)
File : BAB 2 - 181724026.pdf
(541624 bytes)
File : BAB 5 - 181724026.pdf
(172497 bytes)