Motor induksi menjadi mesin listrik yang paling banyak di gunakan di industri sejak awal penemuannya di akhir abad 19. Motor induksi sangat berperan penting sebagai penggerak utama dari mesin-mesin lain seperti fan, pompa dan lain-lain. Kegunaan dan kelebihannya sebagai penggerak utama bukan berarti motor induksi tidak memiliki kekurangan. Salah satu kelemahan dari motor induksi khususnya motor induksi tiga fasa ialah arus pengasutan yang cukup tinggi. Arus pengasutan yang terjadi pada motor induksi tiga fasa dapat mencapai 5-7 kali arus nominalnya bila dilakukan dengan metoda Direct On Line. Hal tersebut dapat mengakibatkan kerusakan pada motor induksi itu sendiri bila lonjakan arus tersebut terjadi terus-menerus dan berulang kali. Untuk mengatasi hal tersebut diperlukan metode dari starting motor induksi yang dapat mengurangi lonjakan arus starting. Salah satu metode yang dapat digunakan adalah menggunakan metode Soft Starting. Soft Starting merupakan metode starting motor induksi dengan membagi tegangan agar masuk secara bertahap ke motor. Komponen utama dari soft starting adalah Thyristor yang akan mengontrol tegangan yang masuk ke motor sehingga tegangan akan masuk ke motor secara bertahap. Pada rancangan ini dilakukan simulasi penggunaan soft starting pada motor HP/IP Feedwater Pump di salah satu PLTGU di Indonesia. Penggunaan soft starter pada rancangan ini terbukti dapat menurunkan lonjakan arus starting menjadi 3,4 kali dari arus nominalnya. Namun disisi lain, penggunaan soft starter membuat motor memerlukan waktu 0,42 s lebih lama untuk mencapai kecepatan nominalnya. Selain itu, penggunaan soft starter menimbulkan adanya harmonisa arus yang terjadi pada orde ganjil selain kelipatan tiga. Kata kunci: arus starting, soft starting, kecepatan nominal, harmonisa.
Deskripsi Alternatif :Induction motors have been the most widely used electric machines in industry since their initial discovery at the end of the 19th century. Induction motors has an important role as prime movers of other machines such as fans, pumps and others. Its usefulness and advantages as a prime mover does not mean that induction motors do not have any weakness. One its weakness especially three-phase induction motors, is the high inrush current. The inrush current that occurs in a three-phase induction motor can reach 5-7 times the nominal current if it is started using the Direct On Line method. This can result in damage to the induction motor itself if the current surge occurs continuously and repeatedly. To overcome this, a method of starting an induction motor which can reduce the inrush current is needed. One of the methods that can be used is using the Soft Starting method. Soft Starting is a method of starting an induction motor by dividing the voltage so that it enters the motor gradually. The main component of soft starting is the Thyristor which will control the voltage entering the motor so that the voltage will enter the motor gradually. In this design, a soft starting simulation was carried out on an HP/IP Feedwater Pump motor in a PLTGU in Indonesia. The use of a soft starter in this design is proven to be able to reduce the starting current surge to 3,4 times the nominal current. But on the other hand, the use of a soft starter makes the motor take 0,42 s longer to reach its nominal speed. In addition, the use of a soft starter causes current harmonics that occur in odd orders except its multiples of three. Keywords: inrush current, soft starting, nominal speed, harmonic.
Beri Komentar ?#(0) | Bookmark
Properti | Nilai Properti |
---|---|
ID Publisher | JBPTPPOLBAN |
Organisasi | |
Nama Kontak | Erlin Arvelina |
Alamat | Jl. Trsn. Gegerkalong Hilir Ds. Ciwaruga |
Kota | Bandung |
Daerah | Jawa Barat |
Negara | Indonesia |
Telepon | 022 201 3789 ext. 168, 169, 239 |
Fax | 022 201 3889 |
E-mail Administrator | erlin.arvelina@polban.ac.id |
E-mail CKO | erlin.arvelina@polban.ac.id |
Print ...
Kontributor...
- Pembimbing 1: Ahmad Deni Mulyadi, S.T., M.T.
Pembimbing 2: Dr. I Made Wiwit Kastawan, S.T., M.T., Editor: Erlin Arvelina
Download...
File : KELENGKAPAN SKRIPSI - 191724004.pdf
(961339 bytes)
File : BAB 1 - 191724004.pdf
(353605 bytes)
File : BAB 2 - 191724004.pdf
(849299 bytes)
File : BAB 5 - 191724004.pdf
(348032 bytes)