Perancangan Sistem Proteksi pada Main Transformator 53,7 MVA Pada PLTA Rajamandala

Design Of Protection System on Main Transformer 53.7 MVA At PLTA Rajamandala

Skripsi, 013 / 2023 / TPTL
Undergraduate Theses from JBPTPPOLBAN / 2024-03-20 11:14:24
Oleh : 191724009 - Fauzan Dzulfiqar (fauzan.dzulfiqar.tptl19@polban.ac.id)
Dibuat : 2024-03-20, dengan 4 file

Keyword : proteksi, transformator, PLTA Rajamandala
Subjek : protection, transformer, PLTA Rajamandala

Transformator merupakan komponen yang sangat penting dalam sistem tenaga listrik oleh karena itu transformator harus dilindungi dari gangguan yang terjadi pada eksternal maupun internal. Proteksi diferensial adalah proteksi yang berfungsi melindungi transformator dari gangguan internal, sementara itu untuk melindungi transformator dari gangguan eksternal maka diperlukan rele arus lebih (OCR) untuk melindungi transformator. Untuk mencegah symphathetic trip, maka perlu adanya analisa terhadap sistem koordinasi proteksi pada pembangkit agar main transformator bisa terlindungi dengan baik. Tugas Akhir ini merancang sistem proteksi untuk main transformator yang memiliki kapasitas sebesar 53.7 MVA dan memiliki tegangan 11/150 kV berupa proteksi diferensial dan proteksi arus lebih untuk melindungi transformator dati gangguan internal dan eksternal. Rancangan proteksi diferensial dapat bekerja dengan baik untuk melindungi gangguan yang terjadi pada internal transformator dengan setting arus pick up sebesar 0.3 A dan dapat melindungi transformator sebesar 87 % ketika gangguan hubung singkat terjadi di dekat titik netral. Hasil simulasi koordinasi proteksi pada sistem pembangkit menunjukkan bahwa sistem koordinasi proteksi dapat berjalan dengan andal, sehingga symphathetic trip dapat dicegah.

Deskripsi Alternatif :

Transformers are very important components in the electric power system, therefore transformers must be protected from external and internal disturbances. Differential protection is a protection that serves to protect the transformer from internal disturbances, while to protect the transformer from external disturbances, an overcurrent relay (OCR) is needed to protect the transformer. To prevent symphathetic trip, it is necessary to analyze the protection coordination system in the power plant so that the main transformer can be well protected. This Final Project designs a protection system for the main transformer which has a capacity of 53.7 MVA and has a voltage of 11/150 kV in the form of differential protection and overcurrent protection to protect the transformer from internal and external disturbances. The differential protection design can work well to protect interference that occurs in the internal transformer with a pick up current setting of 0.3 A and can protect the transformer by 87% when a short circuit fault occurs near the neutral point. The simulation results of protection coordination on the generating system show that the protection coordination system can run reliably, so that symphathetic trip can be prevented.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakErlin Arvelina
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorerlin.arvelina@polban.ac.id
E-mail CKOerlin.arvelina@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: Drs. Ali Mashar, M.Eng.Sc., IPU

    Pembimbing 2: Ahmad Deni Mulyadi, S.T., M.T., Editor: Erlin Arvelina

Download...