Path: Top > Skripsi - D4 > 2017 > Jurusan Teknik Konversi Energi > Program Studi Teknologi Pembangkit Tenaga Listrik > 2023
Rancangan Electronic Load Control 1 Fasa pada Simulator Pembangkit Listrik Tenaga Piko Hidro
Design Of One Phase Electronic Load Control in Pico Hydro Power Plant Simulator
Skripsi, 021 / 2023 / TPTLUndergraduate Theses from JBPTPPOLBAN / 2024-03-20 11:57:27
Oleh : 191724020 - Muhammad Ardhyan Putra Purnama (ardhyanputrapurnama@gmail.com)
Dibuat : 2024-03-20, dengan 4 file
Keyword : Arus, Biner, Phase Angle, ELC, Harmonisa, dan simulator PLTPH
Subjek : Current, Binary, ELC, Harmonics, and PLTPH simulator
Pada sebuah pembangkit listrik tenaga pikohidro (PLTPH) memerlukan adanya kontrol beban konsumen dengan tujuan supaya generator dapat bekerja pada nilai nominalnya dan tidak mengalami kerusakan akibat tidak stabilnya tegangan dan arus keluaran generator. Electronic Load Control (ELC) merupakan salah satu solusi untuk mengatur beban tersebut, namun ELC dipasaran menggunakan konfigurasi beban ballast dengan pengendalian yang memanipulasi gelombang masukannya untuk mengatur besarnya beban ballast, sehingga berakibat pada tingginya harmonisa. Harmonisa merupakan gangguan pada sistem ketenagalistrikan yang akan berdampak buruk bagi generator. Karena hal tersebut maka dirancang ELC yang memiliki harmonisa lebih kecil dengan cara membuat kombinasinya menjadi kombinasi beban ballast metode beban biner dan metode phase angle. Pengujian pada generator yang digunakan mendapatkan hasil beban maksimal generator berada di beban 210 Watt dengan arus sebesar 1 Ampere. Dari data tersebut ditentukan bahwa beban ballast menggunakan 4 buah lampu dengan metode beban biner dimana Lampu 1 bernilai 25 Watt, Lampu 2 bernilai 50 Watt, Lampu 3 bernilai 100 Watt, dan Lampu utama bernilai 200 Watt, lalu 1 buah lampu dengan metode phase angle bernilai 25W. Dengan rancangan tersebut ELC hasil rancangan dapat bekerja dengan baik dibuktikan dengan parameter tegangan generator yang stabil pada tegangan 215V. Hasil pengujian harmonisa pada generator yang digunakan menghasilkan harmonisa yang melebihi standar IEEE 519-1994 dimana harmonisa tegangan sebesar 15%. Karenanya harmonisa tegangan ketika digunakan ELC hasil rancangan berkisar 15.5%. Jika dibandingkan dengan ELC pabrikan yang memiliki harmonisa tegangan sebesar 18%, ELC hasil rancangan ini telah berhasil untuk menurunkan harmonisa sebesar 3% dari ELC pabrikan.
Deskripsi Alternatif :In a pico-hydro power plant (PLTH) it is necessary to control the consumer's load so that the generator does not suffer damage due to unstable generator output voltage and current. Electronic Load Control (ELC) is solution for controlling loads, but ELCs on the market use ballast load configurations with controls that manipulate the input waveform to adjust the ballast load size, that produce high harmonics. Harmonics are disturbances which will have a negative impact on the generator. Therefore an ELC is designed that has smaller harmonics by making the combination a ballast load combination with the binary load method and the phase angle method. Tests on the generator used obtained the results of the maximum generator load at a load of 210 Watt with a current of 1 Ampere. From these data it is determined that the ballast load uses 4 lamps with the binary load method where Lamp 1 is 25 Watt, Lamp 2 is 50 Watt, Lamp 3 is 100 Watt, and the main light is 200 Watt, then 1 lamp with the phase angle method is 25W. With this design, the ELC can work properly as evidenced by the stable generator voltage parameters at 215V. The results of the harmonic test on the generator used produced harmonics that exceeded the IEEE 519-1994 standard where the voltage harmonics were 15%. Therefore, the voltage harmonics when the designed ELC is used is about 15.5%. When compared with the manufacturer's ELC which has a voltage harmonic of 18%, the designed ELC manages to reduce harmonics by 3% of the manufacturer's ELC.
Beri Komentar ?#(0) | Bookmark
Properti | Nilai Properti |
---|---|
ID Publisher | JBPTPPOLBAN |
Organisasi | |
Nama Kontak | Erlin Arvelina |
Alamat | Jl. Trsn. Gegerkalong Hilir Ds. Ciwaruga |
Kota | Bandung |
Daerah | Jawa Barat |
Negara | Indonesia |
Telepon | 022 201 3789 ext. 168, 169, 239 |
Fax | 022 201 3889 |
E-mail Administrator | erlin.arvelina@polban.ac.id |
E-mail CKO | erlin.arvelina@polban.ac.id |
Print ...
Kontributor...
- Pembimbing 1: Apip Pudin, M.Si.
Pembimbing 2: Ir. Wahyu Budi Mursanto, M.Eng., Editor: Erlin Arvelina
Download...
File : KELENGKAPAN SKRIPSI - 191724020.pdf
(795180 bytes)
File : BAB 1 - 191724020.pdf
(721297 bytes)
File : BAB 2 - 191724020.pdf
(1160154 bytes)
File : BAB 5 - 191724020.pdf
(560644 bytes)