Path: Top > Skripsi - D4 > 2017 > Jurusan Teknik Konversi Energi > Program Studi Teknologi Pembangkit Tenaga Listrik > 2023

Rancangan Sistem Kendali pada Backup Line Sistem Seal Water Main Cooling Water Pump PLTP Darajat Menggunakan Pengendali PI

Design Control System of the Backup Line Seal Water Main Cooling Water Pump PLTP Darajat Using PI Controller

Skripsi, 027 / 2023 / TPTL
Undergraduate Theses from JBPTPPOLBAN / 2024-03-20 12:16:53
Oleh : 191724031 - Santi Santika (santi.santika.tptl19@polban.ac.id)
Dibuat : 2024-03-20, dengan 4 file

Keyword : MCWP, Seal, Sistem Seal Water, Kendali PI, Aspen HYSYS
Subjek : MCWP, Seal, Seal Water System, PI Control, Aspen HYSYS

Seal pada Main Cooling Water Pump (MCWP) merupakan salah satu komponen penting yang berfungsi untuk mencegah kebocoran air dari pompa. Sistem seal water diperlukan untuk melumasi dan memelihara seal yang terbuat dari bahan karet dengan sifat mudah aus atau rusak akibat gesekan dan temperatur yang tinggi. Seal perlu dijaga agar tetap bekerja optimal, terdapat standar untuk flow air pada seal water yang ditetapkan oleh PLTP Darajat, yaitu sebesar 5000 kg/h. Namun, dalam proses start up setelah overhaul pada Agustus 2022 nilai flow berada dibawah standar, hal ini disebabkan oleh adanya kotoran yang menumpuk dalam strainer seal. Besarnya flow yang tidak optimal dapat menyebabkan penurunan kinerja dari seal. Bahkan, rendahnya nilai flow air hingga dibawah 1500 kg/h selama tiga menit dapat menyebabkan trip pada MCWP dan trip-nya MCWP menyebabkan trip pada sistem secara keselurahan (trip unit). Software Aspen HYSYS Dynamics digunakan untuk merancangan sistem kendali pada backup line untuk mencegah terjadinya trip dengan menggunakan pengendali PI. Parameter pengendali yang diperoleh, diantaranya pada FIC-101 nilai Kp 2,29 dan Ti 66s diperoleh nilai rise time sebesar 20 s, settling time ± 2% 180 s overshoot 2.878%, undershoot 5,156%, dan steady state error sebesar 0,018%; pada FIC-102 nilai Kp 2,34 dan Ti 66 s diperoleh nilai rise time sebesar 20 s, settling time ± 2% 170 s, overshoot 3,321%, undershoot 4,557%, dan steady state error sebesar 0,193%. Pada pengujian disturbance FIC-101 dan FIC-102, diperoleh nilai maximum undershoot sebesar 1,3% - 1,37%. Kata kunci: MCWP, Seal, Sistem Seal Water, Kendali PI, Aspen HYSYS.

Deskripsi Alternatif :

The seal on the Main Cooling Water Pump (MCWP) is an important component that functions to prevent water leakage from the pump. The water seal system is needed to lubricate and maintain seals made of rubber material which is easily worn or damaged due to friction and high temperatures. Seals need to be maintained so that they continue to work optimally, there is a standard for water flow in seal water set by PLTP Darajat, which is 5000 kg/h. However, during the start-up process after the overhaul in August 2022, the flow value was below standard, this was caused by dirt that had accumulated in the strainer seal. The amount of flow that is not optimal can cause a decrease in the performance of the seal. In fact, a low water flow value below 1500 kg/h for three minutes can cause a trip in the MCWP and a trip in the MCWP causes a trip in the system as a whole (trip unit). Aspen HYSYS Dynamics software is used to design a control system on the backup line to prevent trips by using a PI controller. The controlling parameters obtained, including the FIC-101 value of Kp 2.29 and Ti 66s obtained a rise time value of 20 s, settling time ± 2% 180 s overshoot 2.878%, undershoot 5.156%, and steady state error of 0.018%; on FIC-102, the Kp value is 2.34 and Ti 66 s, the rise time is 20 s, the settling time is ± 2% 170 s, the overshoot is 3.321%, the undershoot is 4.557%, and the steady state error is 0.193%. In the FIC-101 and FIC-102 disturbance tests, the maximum undershoot value was 1.3% - 1.37%. Keywords: MCWP, Seal, Seal Water System, PI Control, Aspen HYSYS.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakErlin Arvelina
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorerlin.arvelina@polban.ac.id
E-mail CKOerlin.arvelina@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: Apip Pudin, M.Si.

    Pembimbing 2: Ir. Wahyu Budi Mursanto, M.Eng., Editor: Erlin Arvelina

Download...