Path: Top > Tugas Akhir - D3 > Jurusan Teknik Konversi Energi > Program Studi Teknik Konversi Energi > 2014

Pembuatan Sistem Ekspansi Pada Sistem Ac Dengan Menggunakan Pipa Kapiler Sebagai Pengganti Fungsi Katup Ekspansi

Making Expansion System At Ac System Using Capillary Substitute As An Expansion Valve Function

Tugas Akhir, 004 / 2014 / TEN
Undergraduate Theses from JBPTPPOLBAN / 2018-04-05 12:34:16
Oleh : Cica Cahyati - 111711035 (cicacahyati1@gmail.com)
Dibuat : 2018-04-05, dengan 4 file

Keyword : pipa kapiler, katup ekspansi, pendingin udara, COP
Subjek : capillary tube, expansion valve, air conditioning, COP

Pada sistem pendingin udara terdapat proses penurunan suhu dan tekanan pada refrigeran tersebut diakibatkan karena proses ekspansi yang terjadi pada pipa kapiler atau katup ekspansi sehingga terjadi kehilangan energi yang secara nyata terlihat adalah penurunan tekanan dan suhu refrigeran menjadi sangat rendah jauh di bawah suhu dan tekanan udara luar. Pada tugas akhir ini penulis akan membuat sistem ekspansi menggunakan pipa kapiler sebagi pengganti dari fungsi katup ekspansi. Untuk dapat membuat sistem tersebut, hal yang dilakukan yaitu memodifikasi trainer refrigerant dengan kapasitas pendingin sebesar 2900 Btu/h yang ada di laboratorium teknik energi (laboratorium bawah). Modifikasi dilakukan dengan membuat sebuah chamber duct yang didalamnya diletakkan sebuah evaporator. Dalam penelitian ini digunakan aplikasi Danffos capillary tube selector (Dancap) untuk menghitung panjang pipa kapiler dengan temperatur kondensasi 41⁰C dan temperatur evaporasi 1,3⁰C . Refrigeran yang digunakan yaitu R-22. Dari aplikasi tersebut diperoleh untuk kapiler 1 sebesar 0,7112 mm, kapiler 2 sebesar 1,1176 mm, kapiler 3 sebesar 1,3208 mm. Pengujian dilakukan untuk menguji ketiga pipa kapiler dan katup ekspansi. Hasil pengujian diperoleh data untuk delta temperature refrigeran sistem pendingin dengan menggunakan katup ekspansi, pipa kapiler 1, pipa kapiler 1, pipa kapiler 1 masing-masing 33,2⁰C, 29,5⁰C, 32,8⁰C dan 27,9⁰C, delta temperatur udara sistem pendingin yaitu masing-masing 4,5⁰C 1,9⁰C, 2,9⁰C dan 2,9⁰C sedangkan untuk COP yaitu 7,196, 6,43, 6,95 dan 6,84. Dari hasil pengujian dan analisa maka disimpulkan pipa kapiler 2 yang baik untuk menggantikan fungsi dari katup ekspansi. Kata kunci: pipa kapiler, katup ekspansi, pendingin udara, COP.

Deskripsi Alternatif :

In air conditioning systems are the temperature and pressure drop in the refrigerant is caused due to the expansion that occurs in a capillary tube or expansion valve causing energy loss which is evident refrigerant pressure drop and temperature becomes very low and well below the temperature of the outside air pressure . In this thesis the author will make system expansion using a capillary tube as a replacement of the expansion valve function. To be able to create such a system, it is done is to modify the trainer refrigerant cooling capacity of 2900 Btu / h's in energy engineering laboratory (lab below). Modifications done by creating a chamber placed inside a duct evaporator. In this study, the application of capillary tube Danffos selector (Dancap) to calculate the length of the capillary condensation temperature of 41⁰C and 1,3⁰C temperature evaporation. The refrigerant used is R-22. Obtained from the application of 0,7112 to 1 mm capillary, capillary 2 was 1,1176 mm, 1,3208 mm for 3 capillaries. Testing was conducted to test the third capillary tube and expansion valve. Test results obtained data for delta temperature refrigeration systems using refrigerant expansion valve, capillary tube 1, 1 capillary, capillary tube 1 respectively 33,2⁰C, 29,5⁰C, 32,8⁰C and 27,9⁰C, delta air temperature cooling system respectively 4,5⁰C, 1,9⁰C, 2,9⁰C and 2,9⁰C, while for the COP is 7,196, 6,43, 6,95 and 6,84. From the test results and analysis, we conclude that both capillary tube 2 to replace the function of the expansion valve. Keywords: capillary tube, expansion valve, air conditioning, COP.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakErlin Arvelina
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorerlin.arvelina@polban.ac.id
E-mail CKOerlin.arvelina@polban.ac.id

Print ...

Kontributor...

  • Pembimbing: Bambang Puguh Manunggal, S.T., M.Eng., Editor: Erlin Arvelina

Download...