Variasi Debit Udara Terhadap Pengurangan Bakteri Pada Ruang Tunggu Puskesmas Sarijadi Menggunakan Fan Cassette Unit

Air Flow Rate Variations Toward Reducing of Bacteria In Waiting Room Sarijadi™s Clinic Using Fan Cassette Unit

Tugas Akhir, 013 / 2016 / RTU
Undergraduate Theses from JBPTPPOLBAN / 2017-09-04 10:43:54
Oleh : Cuci Cahayanti - 131611004 (cuci.cahayanti.trtud13@polban.ac.id)
Dibuat : 2017-08-29, dengan 4 file

Keyword : Air Flow Rate Variations, Reducing of Bacteria, Fan Cassette Unit
Subjek : Variasi Debit Udara, Pengurangan Bakteri, Fan Cassette Unit

Udara ambient mengandung 78% nitrogen, 21% oksigen dan 1% gas-gas lain. Banyak hal berkontribusi terhadap penurunan kualitas udara di dalam ruangan. Pencemar udara yang semakin meningkat diantaranya peralatan yang menghasilkan gas ada di dalam ruangan, asap rokok, bahan kimia lainnya yang sangat menyengat dan partikel debu yang menyebabkan udara di dalam ruangan mengalami pencemaran. Puskesmas mempunyai wewenang dan tanggung jawab atas pemeliharaan kesehatan masyarakat dalam wilayah kerjanya. Sehubungan dengan wewenang dan tanggung jawab tersebut mengharuskan setiap ruangan pada puskesmas memiliki kualitas udara ruangan yang baik, oksigen yang cukup dan pencemar udara yang minimal. Desinfeksi dengan menggunakan sinar ultraviolet merupakan salah satu upaya untuk menghilangkan bakteri pada ruangan. Pemasangan fan cassette unit dilengkapi dengan lampu ultraviolet pada ruang tunggu puskesmas dapat mengurangi pencemaran udara ruangan yang berbentuk bakteri. Pengurangan jumlah bakteri hasil pengujian pemasangan fan cassette unit yang dilengkapi lampu ultraviolet sebesar 65,06% dengan jumlah bakteri yang terhitung persatuan luas yang telah melewati lampu ultraviolet sebesar 1,75CFU/m3 sampai dengan 27,82CFU/m3.

Deskripsi Alternatif :

Ambient air contains 78% nitrogen, 21% oxygen and 1% other gases. Many things contribute to the reduction of indoor air quality. Air pollutants are increasing among gas-producing equipment in the room, cigarette smoke, other chemicals are so terrible and dust particles that cause indoor air pollution experienced. Community Health Centre have the authority and responsibility for the maintenance of public health in the working area. In connection with the authority and responsibility require that every room in the health center has a good indoor air quality, sufficient oxygen and air pollutants are minimal. Desinfection using ultraviolet light is an effort to eliminate bacteria in the room. Installation of the fan cassette unit is equipped with ultraviolet lamps at the health center waiting room can reduce indoor air pollution in the form of bacteria. Reduction in the number of bacteria test results of fan cassette unit installation incorporates ultraviolet lamps for 65,06% of total bacterial count per unit area that has been passed through an ultraviolet lamp for 1,75CFU/m3 up to 27,82CFU/m3.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakErlin Arvelina
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorerlin.arvelina@polban.ac.id
E-mail CKOerlin.arvelina@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: Dr. Pratikto, MT ; Pembimbing 2: Drs. Faldian, M.Eng, Editor: Muhammad Abdillah Islamy, S.Pd

Download...