Rancangan Radiator Pada Sistem Pendingin Transformator Daya Kapasitas 370 MVA Untuk PLTU 2X300 MW

Radiator Design Of 370 MVA Power Transformer Cooling System For 2X300 MW Steam Power Plant

Skripsi, 007 / 2018 / TPTL
Undergraduate Theses from JBPTPPOLBAN / 2019-01-10 08:30:20
Oleh : Eldi Novrizal - 141724009 (eldi.novrizal@gmail.com)
Dibuat : 2019-01-10, dengan 4 file

Keyword : Radiator, Rugi transformator, Nilai faktor kekotoran, Penurunan tekanan, mass flow
Subjek : radiator, loss of transformer, fouling factor, pressure drop, mass flow

Radiator merupakan jenis penukar panas yang digunakan pada sistem pendinginan transformator daya. Radiator berguna untuk melepaskan panas yang terjadi karena proses pembebanan. Minyak transformator pada tangki dialirkan ke radiator untuk selanjutnya akan didinginkan udara. Proses pendinginan ini bertujuan untuk menjaga umur dan unjuk kerja transformator daya. Proses perancangan radiator dimulai dengan menentukan parameter awal yaitu temperatur, laju alir massa, dan panas spesifik, dari minyak transformator dan udara. Kemudian dilakukan perhitungan dimensi sesuai referensi dan analisis hasil rancangan. Besar panas yang dilepas radiator ke udara adalah 1,04 MW, berasal dari besar rugi inti dan rugi belitan. Proses rancangan menghasilkan dimensi pipa berdiameter luar 1,5 inci, ketebalan 0,049 inci, dan panjang 84 inci dengan susunan pipa triangular. Tinggi dan tebal sirip masing-masing 0,78 inci dan tebal 0,098 inci sementara jumlah 8 sirip/inci. Efektivitas radiator sebesar 51,872%, nilai faktor kekotoran sebesar : 0,003008468, penurunan tekanan udara pada sisi duct sebesar 0,04328 psi, dan penurunan tekanan minyak pada sisi pipa sebesar 4,34359 psi. Lalu analisis menunjukan bahwa perubahan mass flow minyak transformator akan berdampak pada penurunan tekanan. Kata kunci: Radiator, Rugi transformator, Nilai faktor kekotoran, Penurunan tekanan, mass flow.

Deskripsi Alternatif :

Radiator is a type of heat exchangers used in power transformers cooling system. Radiator release heat generated by power transformer loading process.Oil in the transformer tank flows into the radiator and then cooled by surrounding air. The purpose of this cooling process is to maintain power transformers lifetime and performance. The radiator design process is started with determining initial parameters such as temperature, mass flow and specific heat, of transformers oil and air. Then calculates the dimension according to references and analyze the design result. Total heat must be released by radiator to the air is found to be 1.04 MW due to transformer core loss and winding loss. The design process result tube dimension of 1.5 inches outer diameter, 0.049 inches thickness and 84 inches length with triangular arrangement. Fin height thickness are 0.78 inches and 0.098 inches respectively while number of fin is 8 fins/inch. The effectiveness of radiator is 51, 872 %, fouling factor is 0.003008468, pressure drop in duct size is 0.04328 psi, and pressure drop in tube side is 4.34359 psi. Analysis then show that changes of transformers oil mass flow will affect the pressure drop. Keywords: radiator, loss of transformer, fouling factor, pressure drop, mass flow.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakErlin Arvelina
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorerlin.arvelina@polban.ac.id
E-mail CKOerlin.arvelina@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: Dr. I Made Wiwit Kastawan, M.T.

    Pembimbing 2: Dr. Ir. Sri Wuryanti, M.Si., Editor: Erlin Arvelina

Download...