Pemilihan Jenis dan Perancangan Filler untuk Modifikasi Filler pada Cooling Tower di PLTP Gunung Salak
Selection of Filler Type and Design for Filler Modification in Cooling Tower at PLTP Gunung Salak
Skripsi, 009 / 2021 / TKEUndergraduate Theses from JBPTPPOLBAN / 2022-12-28 13:01:49
Oleh : Hafizh Taruna Subagdja - 171734010 (hafizh.taruna.tken417@polban.ac.id)
Dibuat : 2022-12-28, dengan 4 file
Keyword : Cooling Tower, Filler, Film Fill , Approach, Range, Efektivitas
Subjek : Cooling Tower, Filler, Heat Transfer, Range, ASPEN PLUS, Effectiveness, Cooling Capacity
Cooling Tower merupakan salah satu komponen yang sangat peting bagi suatu Pembangkit Listrik Tenaga Bumi (PLTP). Cooling Tower di PLTP Gunung Salak menggunakan siklus terbuka (Open Loop) dimana air dan udara yang digunakan menggunakan sumber dari lingkunga sekitar. Air panas hasil pendinginan keluaran steam turbin yang masuk ke kondesor akan diubah fasa menjadi air, dimana air panas yang keluar dari kondensor akan masuk kedalam Cooling Tower untuk didinginkan. Selanjutnya air dingin yang keluar dari Cooling Tower disirkulasikan kembali menuju kondensor untuk mendinginkan uap panas dari turbin dan begitu seterusnya. Karena kaitannya yang sangat erat, maka kinerja dari Cooling Tower dapat menentukan kinerja dari turbin dan kondensor. Cooling Tower pada PLTP Gunung Salak sudah beroperasi lebih dari 20 tahun sehingga mengalami penurunan kinerja dimana suhu air yang keluar dari Cooling Tower mengalami kenaikan sebesar 32,2oC. Hal ini mengakibatkan nilai dari Range menjadi turun, dikarenakan perpidahan panas yang terjadi pada Cooling Tower sudah tidak efektif dan memerlukan penggantian Filler. Terdapat beberapa jenis Filler baru di pasaran dengan ukuran dan luas permukaan yang bervariasi. Oleh karena itu, laporan ini akan melakukan modifikasi dengan memilih jenis dan bentuk serta ukuran filter dengan rancangan baru diharapkan. Diharapkan Filler hasil modifikasi dapat memberikan nilai perpindahan panas yang efektif dan mencapai Range 15-25oF (Ludwig, 1997). Metode kuantitatif digunakan dimana data primer didapatkan dari data operasi PLTP Gunung Salak sedangkan data sekunder serta penunjang dari berbagai jurnal dan buku teks. Didapatkan hasil dari rancangan Filler memenuhi kriteria perancangan, yaitu nilai pressure drop < 2 inH2O. Adapun, berdasarkan data hasil simulasi dengan software ASPEN PLUS didapatkan temperatur air keluaran Cooling Tower dengan Filler hasil rancangan, yaitu suhu air yang keluar menjadi 30,87oC. Terjadi peningkatan nilai Range hasil rancangan menjadi 15,13oC, sehingga efektivitas Cooling Tower juga meningkat menjadi 52,53% (kapasitas pendinginan naik menjadi 23.748.048 kcal/h). Analisis keekonomian menghasilkan Payback Period 6,5 bulan dan nilai NPV Rp.148.909.759.532. Kata Kunci: Cooling Tower, Filler, Film Fill , Approach, Range, Efektivitas.
Deskripsi Alternatif :Cooling Tower is one of the components that are very important for an Earth Power Plant (PLTP). Cooling Tower in PlTP Mount Salak uses an open cycle (Open Loop) where water and air are used using sources from the surrounding environment. Hot water from cooling the steam turbine output that goes into the condeser will be converted phase into water, where hot water coming out of the condenser will enter the Cooling Tower to be cooled. Furthermore, the cold water coming out of the Cooling Tower is recirculated back to the condenser to cool the hot steam from the turbine and so on. Because of its close relationship, the performance of the Cooling Tower can determine the performance of the turbine and condenser. Cooling Tower at Mount Salak PLTP has been operating for more than 20 years so that it has decreased performance where the water temperature coming out of the Cooling Tower has increased by 32.2oC. This causes the value of the Range to decrease, because the heat weaning that occurs in the Cooling Tower is not effective and requires filler replacement. There are several new types of fillers on the market with varying sizes and surface areas. Therefore, this report will make modifications by choosing the type and shape and size of the filter with the expected new design. It is expected that the modified filler can provide an effective heat transfer value and reach a range of 15-25oF (Ludwig, 1997). Quantitative methods are used where primary data is obtained from Gunung Salak PLTP operating data while secondary data and support from various journals and textbooks. The results of filler design meet the design criteria, namely pressure drop value < 2 inH2O. Meanwhile, based on simulation data with ASPEN PLUS software obtained the water temperature of cooling tower output with filler design results, namely the water temperature that came out to 30.87oC. There was an increase in the range value of the design results to 15.13oC, so the effectiveness of the Cooling Tower also increased to 52.53% (cooling capacity rose to 23,748,048 kcal / h). Economic analysis resulted in a Payback Period of 6.5 months and an NPV value of Rp.148,909,759,532. Keywords: Cooling Tower, Filler, Heat Transfer, Range, ASPEN PLUS, Effectiveness, Cooling Capacity.
Beri Komentar ?#(0) | Bookmark
Properti | Nilai Properti |
---|---|
ID Publisher | JBPTPPOLBAN |
Organisasi | |
Nama Kontak | Erlin Arvelina |
Alamat | Jl. Trsn. Gegerkalong Hilir Ds. Ciwaruga |
Kota | Bandung |
Daerah | Jawa Barat |
Negara | Indonesia |
Telepon | 022 201 3789 ext. 168, 169, 239 |
Fax | 022 201 3889 |
E-mail Administrator | erlin.arvelina@polban.ac.id |
E-mail CKO | erlin.arvelina@polban.ac.id |
Print ...
Kontributor...
- Pembimbing 1: Drs. Maridjo, M.T.
Pembimbing 2: Annisa Syafitri K., S.ST., M.Sc., Editor: Erlin Arvelina
Download...
File : KELENGKAPAN SKRIPSI - 171734010.pdf
(1049987 bytes)
File : BAB 1 - 171734010.pdf
(71770 bytes)
File : BAB 2 - 171734010.pdf
(1122119 bytes)
File : BAB 5 - 171734010.pdf
(60607 bytes)