Path: Top > Jurnal Ilmiah > Jurusan Teknik Kimia > In Jumanda Kasdadi

Simulasi Skenario Ledakan Tangki Butana dan Metana pada PLTP Dieng Unit 2 Menggunakan Software ALOHA

Simulation of Butane and Methane Tank Explosion Scenarios at Unit 2 Dieng Geothermal Power Plant Using ALOHA Software

Journal from JBPTPPOLBAN / 2022-02-23 10:15:39
Oleh : In Jumanda Kasdadi - 196809201995121001 (in.jumanda@polban.ac.id)
Dibuat : 2021-11-08, dengan 1 file

Keyword : keselamatan kerja, bahaya ledakan, simulasi, ALOHA

Tangki yang akan digunakan untuk menyimpan butana dan metana di PLTP Dieng Unit 2 mengandung bahaya kebakaran dan peledakan jika terjadi pecah. Untuk kepentingan kesehatan dan keselamatan kerja, besarnya bahaya ini perlu untuk diperkirakan sebelum PLTP dibangun agar tidak membahayakan bagi manusia, fasilitas,lingkungan, termasuk penduduk di sekitar PLTP Dieng Unit 2. Simulasi skenario ledakan tangki butana dan metana pada PLTP Dieng Unit 2 ini menggunakan Software ALOHA. Dengan skenario terburuk yaitu pecahnya tangki penampung Butana dan Pentana pada alur proses Organic Rankine Cycle (ORC) di Dieng Unit 2, menggunakan pendekatan asumsi volume, menghasilkan jarak zona ancaman merah (flame pocket) 335 meter (konsentrasi 9600 ppm), sedangkan zona ancaman kuning 885 meter (1600 ppm). Skenario mitigasi yang disarankan adalah pemasangan blast wall di area storage tank sehingga area ledakan memiliki short impact. Desain bejana penyimpanan berbentuk bola yang baik untuk butana dan pentana juga direkomendasikan.

Deskripsi Alternatif :

The pressure vessel to be used to store butane and methane at the Dieng Unit 2 PLTP contains a fire and explosion hazard in the event of a rupture. In the interest of occupational health and safety, the magnitude of this hazard needs to be estimated before the PLTP is built so as not to endanger humans, facilities, the environment, including residents around the Dieng Unit 2 PLTP. Simulation of the butane and methane tank explosion scenario at the Dieng Unit 2 PLTP uses software ALOHA. With the worst scenario, namely the rupture of the Butane and Pentane storage tanks in the Organic Rankine Cycle (ORC) process flow at Dieng Unit 2, with an approach for volume assumption, resulting the distance of red threat zone (flame pocket) of 335 meters (9600 ppm concentration), while the yellow threat zone 885 meters (1600 ppm). The recommended mitigation scenario is the installation of a blast wall in the storage tank area so that the explosion area has a short impact. A good design of spherical storage vessel for butane and pentane is also recommended.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakErlin Arvelina
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorerlin.arvelina@polban.ac.id
E-mail CKOerlin.arvelina@polban.ac.id

Print ...

Kontributor...

  • , Editor: Erlin Arvelina

Download...