Path: Top > Skripsi - D4 > Jurusan Teknik Sipil > Prodi Teknik Perawatan & Perbaikan Gedung > 2016
Perencanaan Ulang Sistem Penyediaan Air Bersih di Gedung I, Gedung II, dan Gedung Penghubung LAPAN Bandung
Redesign of Clean Water Supply System in Building I, Building II, and Connecting Building of LAPAN Bandung
Tugas Akhir, 002 / 2016 / TPPGUndergraduate Theses from JBPTPPOLBAN / 2018-09-03 15:06:04
Oleh : Kathy Sulistianny - 121144014 (sulistiannykathy@gmail.com)
Dibuat : 2017-07-27, dengan 4 file
Keyword : Sistem Penyediaan Air Bersih, Kebutuhan Air Bersih, Reservoir, Pompa
Subjek : Clean Water Supply System, Clean Water Necessity, Reservoir, Pump
LAPAN Bandung terletak di Jl. Doktor Djunjunan No.133 Bandung yang berdiri sejak tahun 1980. LAPAN Bandung ini memiliki tiga sumber air bersih yaitu sumur dalam (Deep Well). Khusus bagi Gedung I, Gedung II lantai 3 dan Gedung Penghubung berasal dari Sumur 1, dan bagi Gedung II lantai 1 dan 2 berasal dari sumur II. Setelah dilakukan pengujian debit pompa submersible pada sumur I didapat debit rata-rata sebesar 4,77 liter/detik. Namun terdapat masalah pada sistem penyediaan air bersih di LAPAN Bandung ini terutama pada Gedung I dan Gedung Penghubung yang memiliki sumber yang sama (Sumur I) yaitu terjadi kekurangan air bersih karena beban unit yang terlalu besar. Perencanaan ulang sistem penyediaan air bersih ini dimulai dengan menghitung kebutuhan air bersih pada Gedung yang dilakukan dengan dua cara yaitu berdasarkan jumlah hunian dan berdasarkan beban unit alat plambing, langkah selanjutnya adalah menghitung kapasitas reservoir yang dibutuhkan, kemudian dilanjutkan dengan merencanakan diameter pipa dengan menggunakan nomogram debit dan diameter pipa, selanjutnya melakukan perhitungan dimensi distribution line dan pompa air bersih, dan yang terakhir adalah menghitung rencana anggaran biaya yang diperlukan untuk merealisasikan sistem penyediaan air bersih yang direncanakan. Berdasarkan hasil perencanaan sistem penyediaan air bersih, diperoleh kebutuhan air bersih pada gedung yang digunakan yaitu berdasarkan beban unit alat plambing sebesar 5,833 liter/detik, kapasitas reservoir bawah yang dibutuhkan sebesar 30,614 m3, kapasitas reservoir atas yang dibutuhkan sebesar 13,25 m3, kapasitas pompa yang dibutuhkan sebesar 350 liter/menit dengan tinggi total 43,37 meter dan daya motor penggerak pompa sebesar 4,923 kW, dan biaya yang dibutuhkan untuk merealisasikan sistem penyediaan air bersih yang telah direncanakan ini sebesar Rp. 140.870.000,00. Kata Kunci: Sistem Penyediaan Air Bersih, Kebutuhan Air Bersih, Reservoir, Pompa.
Deskripsi Alternatif :LAPAN Bandung is located in Jl. Doktor Djunjunan No. 133 Bandung which is built in 1980. LAPAN Bandung has three clean water sources, it called Deep Well. First Well is supplying Building 1, the third floor of Building II, and connecting building. Second Well is supplying the first and second floor of Building II. After submersible pump debit test in First Well, it gets average debit 4,77 liters/second. But there is a problem in clean water supply system of LAPAN Bandung specifically in Building 1 and connecting building which is supplied from the same well (First Well) and there is a lack of clean water supply because of the large of unit load. Redesign of clean water supply system is started with counting clean water necessity at the building with two ways there are counting by the people in the building and unit load of plumbing devices, the next step is counting the capacity of reservoir that it needs, the third step is designing pipe diameter with debit and pipe diameter monogram, the fourth step is counting dimension of distribution line and clean water pump, and the last step is counting estimated cost for applying the design of clean water supply system. Referred in clean water supply system design result, it gets clean water necessity at the building by unit load of plumbing devices is 5,833 liters/second, the capacity of ground reservoir is 30,614 m3, the capacity of roof reservoir is 13,25 m3, the capacity of pump is 350 liters/minute with the total head is 43,34 meters and pump power is 4,933 kW, and the cost for applying design of clean water supply system is Rp. 140.870.000,- Keywords: Clean Water Supply System, Clean Water Necessity, Reservoir, Pump.
Beri Komentar ?#(0) | Bookmark
Properti | Nilai Properti |
---|---|
ID Publisher | JBPTPPOLBAN |
Organisasi | |
Nama Kontak | Erlin Arvelina |
Alamat | Jl. Trsn. Gegerkalong Hilir Ds. Ciwaruga |
Kota | Bandung |
Daerah | Jawa Barat |
Negara | Indonesia |
Telepon | 022 201 3789 ext. 168, 169, 239 |
Fax | 022 201 3889 |
E-mail Administrator | erlin.arvelina@polban.ac.id |
E-mail CKO | erlin.arvelina@polban.ac.id |
Print ...
Kontributor...
- Pembimbing 1: Ahmad Sofyan, S.ST., M.Eng.
Pembimbing 2: Rahmat Permana, S.ST., M.Eng., Editor: Erlin Arvelina
Download...
File : KELENGKAPAN TA - 121144014.pdf
(504688 bytes)
File : BAB 1 - 121144014.pdf
(461923 bytes)
File : BAB 2 - 121144014.pdf
(829270 bytes)
File : BAB 6 - 121144014.pdf
(396619 bytes)