Path: Top > Tugas Akhir - D3 > Jurusan Teknik Refrigerasi dan Tata Udara > Program Studi Teknik Refrigerasi dan Tata Udara > 2012

PENGONTROLAN BEDA TEKANAN UDARA DENGAN VARIASI BUKAAN DAMPER DAN KECEPATAN FAN BERBASIS MIKROKONTROLER ARDUINO MEGA 2560 PADA MODEL RUANG OPERASI

AIR PRESSURE DIFFERENCE CONTROLLING BY VARIATING THE DAMPER OPENING AND FAN SPEED BASED ON ARDUINO MEGA 2560 MICROCONTROLLER ON OPERATING ROOM

Tugas Akhir, 005 / 2012 / RTU
Undergraduate Theses from JBPTPPOLBAN / 2014-06-19 15:07:33
Oleh : Luthfi Merdiandani - 091611077 (merdi.luthfi@gmail.com)
Dibuat : 2014-06-19, dengan 4 file

Keyword : pengontrolan tekanan udara, ruang operasi, beda tekanan, bukaan damper, kecepatan fan, Arduino Mega 2560, BMP085, shield Arduino
Subjek : controlling air pressure, operating room, difference air pressure, aperture damper, fan speed, Arduino Mega 2560, BMP085, Shield Arduino

Pengontrolan tekanan udara secara otomatis merupakan hal yang penting diterapkan di ruang operasi untuk menghindari adanya kontaminasi bakteri antara luar ruangan dengan dalam ruangan dengan nilai beda tekanan minimal 12 Pa lebih tinggi dari tekanan lingkungan. Pengontrolan tekanan udara ruangan dilakukan dengan mengatur debit udara masuk dan keluar ruangan. Model ruang operasi yang dibuat, dirancang untuk dapat mengontrol beda tekanan udara dengan cara mengatur bukaan damper dan kecepatan fan agar dapat menghasilkan nilai beda tekanan ruangan yang lebih stabil. Alat kontrol yang digunakan adalah mikrokontroler Arduino Mega 2560 yang dilengkapi dengan shield Control Motor DC, LCD, dan SD Card Arduino. Sensor tekanan menggunakan BMP085 dan penggerak damper menggunakan motor servo. Hasil akhir yang didapat adalah set point nilai beda tekanan udara dapat dikontrol sesuai dengan perubahan tekanan lingkungan dengan beda tekanan udara antara 12–25 Pa dan tekanan udara ruangan dapat diatur antara 92174–92185 Pa dengan nilai beda tekanan antara 54–15 Pa atau rata-rata sebesar 32,56 Pa lebih tinggi dari tekanan udara lingkungan. Kata kunci: pengontrolan tekanan udara, ruang operasi, beda tekanan, bukaan damper, kecepatan fan, Arduino Mega 2560, BMP085, shield Arduino.

Deskripsi Alternatif :

Controlling the air pressure automatically which is applied in the operating room is important to avoid the contamination of bacteria between outdoors and indoors with air pressure difference of 12 Pa above atmospheric air pressure around the room. Controlling the air pressure in the room can be done by regulating the air flow in and out of the room. The operating room model that was made, designed to control the air pressure difference between by combining the aperture damper settings and fan speed in order to generate the room pressure difference to be more constant .The controller which is used in this project is Arduino2560 that is equipped with a DC Motor Control, LCD, and SD Card Shield Arduino. Pressure sensor is BMP085 and the damper is moved by servo motor. The set point of air pressure difference can be controlled by using ambient pressure change with range between 12–25 Pa and room air pressure can be controlled by using range of 92174–92185 Pa with average pressure difference is about 32,56 Pa which higher than ambient air pressure. Key word: controlling air pressure, operating room, difference air pressure, aperture damper, fan speed, Arduino Mega 2560, BMP085, Shield Arduino.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakErlin Arvelina
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorerlin.arvelina@polban.ac.id
E-mail CKOerlin.arvelina@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: Edmond Murad, ST.

    Pembimbing 2: Muhammad Arman, ST., S.Psi.
    , Editor: Erlin Arvelina

Download...