Rancangan Proteksi Ground Fault Relay untuk Generator Kapasitas 802 MVA

The Design of Ground Fault Relay Protection for Generator with the Capacity of 802 MVA

Skripsi, 012 / 2018 / TPTL
Undergraduate Theses from JBPTPPOLBAN / 2019-01-10 08:50:50
Oleh : Maula Zahara Firdausi - 141724014 (maulazaharaf@gmail.com)
Dibuat : 2019-01-10, dengan 4 file

Keyword : tegangan harmonik ketiga, neutral ground transformer (NGT), overvoltage ground neutral relay, undervoltage third harmonic relay
Subjek : third harmonic voltage, neutral ground transformer (NGT), overvoltage ground neutral relay, undervoltage third harmonic relay

Generator merupakan bagian yang sangat esensial pada suatu pembangkit listrik karena komponen inilah dilakukan proses konversi energi mekanik menjadi listrik, di samping juga sangat mahal. Oleh karena itu, generator harus diproteksi pada tingkat yang sangat tinggi dari potensi gangguan yang dapat terjadi, baik secara internal maupun eksternal agar terhindar dari kerusakan fatal. Gangguan-gangguan ini umumnya diatasi dengan overcurrent relay (OCR) dan differential protection relay. Dikarenakan keterbatasan jangkauan kerjanya, relay-relay proteksi tersebut tidak mampu mengatasi gangguan internal yang terjadi di dekat titik netral stator generator. Tugas akhir ini membahas rancangan sistem proteksi yang mampu mengatasi gangguan yang dimaksud dengan mengamankan 100% belitan stator generator, dari ujung terminal sampai titik netralnya. Sistem proteksi yang dirancang merupakan gabungan antara neutral ground overvoltage relay (59GN) dan undervoltage third harmonic relay (27T). Dalam perancangan proteksi ini membutuhkan data spesifikasi teknis generator dan sistem pembumian netralnya. Sistem pembumian netral yang dipilih dan sesuai dengan kapasitas generator adalah jenis NGT (neutral grounded transformer). Kemudian dilakukan perhitungan arus kesalahan dan tegangan harmonisa ketiga yang terjadi serta ditentukan setting relay-relaynya. Hasil rancangan menunjukkan bahwa kombinasi antara relay 59GN dan 27T cukup efektif untuk memproteksi 100% kumparan stator dengan setting relay 59GN; 190 V dengan delay time 1 detik; setting relay 27T; 94 V dengan delay time 1 detik. Selain itu, kedua relay memiliki overlapping 29,87% dengan neutral grounded transformer (NGT) mempunyai kapasitas 28,29 kVA, 15000/240 V dan Rsec 0,38Ω. Kata kunci: tegangan harmonik ketiga, neutral ground transformer (NGT), overvoltage ground neutral relay, undervoltage third harmonic relay.

Deskripsi Alternatif :

Generator is the essential part of powerplant system because there happened energy conversion from mechanical into electrical energy, besides generator is relatively expensive. So, it should be protected from any internal or external faults that could damage the generator. These faults are commonly overcome by overcurrent relay (OCR) and differential protection relay. Both of those relays can't detect the faults near the generator stator neutral point due to the limited range of operation. This thesis discusses about the protection system that is able to overcome those faults by protecting 100% of generator stator winding from the end of terminal to the neutral end. The design of this protection system is the combination between neutral ground overvoltage relay (59GN) and undervoltage third harmonic relay (27T). The designing process needs generator's data specification and its grounding method. NGT (neutral grounded transformer) is selected based on generator's capacity. Then, short circuit current, third harmonic voltage and setting relays are calculated. The design results show that the combination of 59GN and 27T relay is quite effective to protect 100% generator stator winding with setting of 59GN relay; 190V, 1 second delay time. Setting of 27T relay; 94 V, 1 second relay time. Both relays have overlapping 29,87% with NGT grounding method the capacity 28,29 kVA, 15000/240 V and Rsec 0,38Ω. Keywords: third harmonic voltage, neutral ground transformer (NGT), overvoltage ground neutral relay, undervoltage third harmonic relay.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakErlin Arvelina
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorerlin.arvelina@polban.ac.id
E-mail CKOerlin.arvelina@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: Drs. Ali Mashar, M.Eng.Sc.

    Pembimbing 2: Ahmad Deni Mulyadi, S.T., M.T., Editor: Erlin Arvelina

Download...