Pembangkit listrik tenaga air merupakan pembangkitan listrik yang menggunakan energi potensial air. PLTA Cirata merupakan PLTA terbesar yang ada di Indonesia dengan kapasitas pembangkitan sebesar 1008 MW. Sistem utama pembangkitan pada sebuah PLTA membutuhkan alat penunjang untuk menjaga kondisi mesin seperti Cooling Water Pump (CWP), yang digunakan untuk mendinginkan oli pelumas untuk Thrust Bearing Oil Cooler, Turbine Guide Bearing Oil Cooler, Governor Oil Cooler, dan Generator Air Cooler. Beberapa masalah seringkali membuat cooling water pump tidak dapat bekerja dengan optimal, gangguan misalignment loseness yang dapat menimbulkan vibrasi yang berlebih dan akan merusak sistem dari cooling water pump, seperti mesin panas, kehilangan torsi dan kerusakan berlanjut akibat misalignment. Untuk mengetahui kondisi mesin dapat dilakukan dengan vibration monitoring menggunakan alat vibration analyzer, data yang didapat berupa kecepatan vibrasi. ISO 10816-3 digunakan untuk membandingkan dan membuat kategori kondisi motor dan pompa, dengan batas dimana motor yang dapat dikategorikan rusak apabila sudah melewati kecepatan vibrasi sebesar 7,1 mm/s dan mesin yang di kategorikan dalam kondisi baik bila vibrasi mekanik lebih kecil dari 2,3 mm/s Konsumsi energi listrik juga dipegaruhi oleh besarnya vibrasi pada CWP. Pada kondisi kecepatan vibrasi sebesar 8,5 mm/s konsumsi daya meningkat hingga 126 kW dan pada pengoperasian CWP unit I pada kondisi offset sebesar 1,61 mm/s menunjukkan kondisi kritis, dengan peningkatan konsumsi sebesar 6,92 % pada konsumsi energi sebesar 122 kW. Kata kunci: misalignment, vibrasi, motor induksi, konsumsi listrik.
Deskripsi Alternatif :Hydroelectricity is electricity generation that uses the potential energy of water. PLTA Cirata is the largest hydroelectric power plant in Indonesia with a total capacity of 1008 MW. Main system at a hydropower generation requires a supporting tool to maintain the condition of the machine such as Cooling Water Pump (CWP), which is used to cool the lubricating oil for Thrust Bearing Oil Cooler, Turbine Guide, Bearing Oil Cooler, Oil Cooler Governor, and Generator Air Cooler. Some problems often make cooling water pump can not work optimally, looseness misalignment disorder that can cause excessive vibration and damage the system of cooling water pump, such as a hot engine, the torque loss and damage caused misalignment continues. To determine the condition of machine vibration monitoring can be done by using a vibration analyzer, the data obtained in the form of vibration velocity. ISO 10816-3 is used to compare and categorize the condition of the motor and pump, to the extent that the motor can be considered defective if it has passed the vibration speed of 7.1 mm/s and machines are categorized in good condition when mechanical vibration is smaller than 2.3 mm/s. Electrical energy consumption also been affected by the magnitude of vibration at CWP. When conditions of vibration velocity of 8.5 mm/s power consumption increased to 126 kW and the operation of the first unit on condition CWP offset of 1.61 mm/s indicates a critical condition , with a 6.92 % increase in consumption in energy consumption by 122 kW. Keywords: misalignment, vibration, induction motor, electricity consumption.
Beri Komentar ?#(0) | Bookmark
Properti | Nilai Properti |
---|---|
ID Publisher | JBPTPPOLBAN |
Organisasi | |
Nama Kontak | Erlin Arvelina |
Alamat | Jl. Trsn. Gegerkalong Hilir Ds. Ciwaruga |
Kota | Bandung |
Daerah | Jawa Barat |
Negara | Indonesia |
Telepon | 022 201 3789 ext. 168, 169, 239 |
Fax | 022 201 3889 |
E-mail Administrator | erlin.arvelina@polban.ac.id |
E-mail CKO | erlin.arvelina@polban.ac.id |
Print ...
Kontributor...
- Pembimbing: Ir. Conny K. Wachjoe, M.Eng., Ph.D., Editor: Erlin Arvelina
Download...
File : DAFTAR - 101711054.pdf
(889592 bytes)
File : BAB 1 - 101711054.pdf
(240926 bytes)
File : BAB 2 - 101711054.pdf
(654770 bytes)
File : BAB 5 - 101711054.pdf
(231016 bytes)