Perancangan Chiller Water Cooled Condenser Kapasitas 155 TR Pengkondisian Udara Ruang Produksi Vaksin

Designing Chiller Water Cooled Condenser With 155 TR Capacity For Air Conditioning Production Room

Skripsi, 021 / 2019 / TKE
Undergraduate Theses from JBPTPPOLBAN / 2019-12-12 12:13:46
Oleh : Putri Hanifah Sasmitoningrum - 151734021 (putrihanifahs.ph@gmail.com)
Dibuat : 2019-12-12, dengan 4 file

Keyword : efektivitas, kondensor, maintenance, refrigerasi, R134a
Subjek : effectiveness, condenser, maintenance, refrigeration, R134a

Industri farmasi merupakan salah satu industri yang selalu menggunakan sistem pendingin udara dalam proses produksi vaksin. Sistem pengkondisian udara ruang vaksin menggunakan proses pendinginan sistem refrigerasi kompresi uap, yang memiliki 4 komponen utama, yaitu kompresor, kondensor, katup ekspansi, dan evaporator. Refrigeran yang digunakan untuk pendinginan ruangan ini adalah R134a. Dari 4 komponen tersebut, kondensor berperan penting dalam melakukan pelepasan energi panas ke lingkungan karena adanya proses tukar kalor. Kondensor yang awalnya berjenis air cooled dimana menggunakan udara sebagai media tukar kalor, menimbulkan masalah berupa maintenance yang terlalu berkala dan temperatur keluaran kondensor yang sudah tidak mencapai set poin yang diinginkan sehingga dilakukan penggantian menjadi water cooled. Jenis penukar kalor yang digunakan adalah shell and tube, penggatian ini dapat mempengaruhi nilai temperatur keluaran kondensor, efekvitias pada alat, dan COP (Coefficient of Performace) pada sistem. Penelitian ini menggunakan metode kuantitatif dimana data yang digunakan adalah data primer dan sekunder. Data dianalisa berdasarkan hasil perhitungan yang menggunakan metode D.Q Kern dan simulasi menggunakan perangkat lunak Aspen HYSYS untuk mengetahui parameter prosesnya dan EDR (Exchanger Design and Rating) untuk mengetahui parameter design. Hasil dari perancangan water cooled condenser tipe shell and tube memiliki temperatur keluaran kondensor sebesar 9,23℃ yang semula 26℃, peningkatan efektivitas dengan nilai 0,67 yang semula 0,61, nilai COP yang semula bernilai 2,82 menjadi 4,83 dan peluang penghematan energi dari perancangan water cooled condenser ini mencapai 3084, 51 kWh/hari. Kata Kunci: efektivitas, kondensor, maintenance, refrigerasi, R134a.

Deskripsi Alternatif :

The pharmaceutical industry is one industry that always uses air conditioning systems in the vaccine production process. Vaccine room air conditioning system uses a cooling process of the steam compression refrigeration system, which has 4 main components, namely compressor, condenser, expansion valve, and evaporator. The refrigerant used for cooling this room is R134a. Of the 4 components, the condenser plays an important role in releasing heat energy into the environment because of the heat exchange process. The condenser which was originally air cooled type which uses air as a heat exchange media, causes problems in the form of maintenance that is too periodic and the condenser output temperature has not reached the desired set point so that it is replaced with water cooled. The type of heat exchanger used is shell and tube, this replacement can affect the value of the condenser output temperature, the effect on the device, and the COP (Coefficient of Performace) on the system. This study uses quantitative methods in which the data used are primary and secondary data. Data were analyzed based on the results of calculations using the D.Q Kern method and simulations using Aspen HYSYS software to determine the process parameters and EDR (Exchanger Design and Rating) to determine the design parameters. The results of the design of shell and tube water cooled condenser have a condenser output temperature of 9.23℃ which was originally 26℃, increased effectiveness with a value of 0.67 which was originally 0.61, COP value which was originally valued at 2.82 to 4.83 and the opportunity for savings energy from the design of this water cooled condenser reaches 3084, 51 kWh / day. Keywords: effectiveness, condenser, maintenance, refrigeration, R134a.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakErlin Arvelina
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorerlin.arvelina@polban.ac.id
E-mail CKOerlin.arvelina@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: Dr. Ir. Sapto Prajogo, M.Si.

    Pembimbing 2: Dr. Ir. Sri Wuryanti, M.Si., Editor: Erlin Arvelina

Download...