ANALISIS PERFORMANSI SISTEM REFRIGERASI KOMPRESI UAP UNTUK PENYIMPANAN WHOLE BLOOD PADA MINI BLOOD BANK CABINET

ANALYSIS OF PERFORMANCE OF VAPOUR COMPRESSION REFRIGERATION SYSTEM FOR WHOLE BLOOD ON MINI BLOOD BANK CABINET

Tugas Akhir, 014 / 2012 / RTU
Undergraduate Theses from JBPTPPOLBAN / 2014-06-19 15:57:36
Oleh : Rizky Aliya - 091611026 (aliyarizky@gmail.com)
Dibuat : 2014-06-19, dengan 4 file

Keyword : Blood Bank Cabinet, coefficient of performance, performance efficiency
Subjek : Blood Bank Cabinet, coefficient of performance, performance efficiency

Blood Bank Cabinet adalah suatu alat yang digunakan untuk penyimpanan darah dengan menjaga temperatur antara 1°-6°C. Untuk mengetahui kinerja sistem, maka sistem tersebut harus diuji. Tujuan dari karya ilmiah ini adalah untuk mengetahui besarnya performansi sistem dan menganalisis kinerja sistem. Metode yang digunakan pada karya ilmiah ini adalah dengan melakukan pengujian pada mini Blood Bank Cabinet dan mengumpulkan data dari pengujian tersebut. Produk contoh digunakan pada pengujian adalah darah dengan volume 350 ml. Hasil dari pengujian dan perhitungan adalah bahwa nilai rata-rata coefficient of performance adalah 3.62, efisiensi sistem rata-rata sebesar 54.2%, temperatur kabin 1°-6°C, temperatur akhir produk 4.2°C, dan daya sebesar 319.5 watt. Kata kunci : Blood Bank Cabinet, coefficient of performance, performance efficiency

Deskripsi Alternatif :

Blood Bank Cabinet is a cabinet which is used for blood storage which maintain the temperature of 1°-6°C. To obtain performance of system, the system must be tested. The aims of this final project is to obtain the performance of system. The method used in this final project are by doing experiment to a mini Blood Bank Cabinet and collecting data from the experiment. The sample product used in experiment is blood with volume of 350 ml. The results of the study show that the value of coefficient of performance is 3.62, performance efficiency is 54.2%, cabin temperature 1°-6°C, product temperature 4.2°C, and power 319.5 watt. Keywords : Blood Bank Cabinet, coefficient of performance, performance efficiency

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakErlin Arvelina
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorerlin.arvelina@polban.ac.id
E-mail CKOerlin.arvelina@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: Ir. Arda Rahardja Lukitobudi, M.Eng.

    Pembimbing 2: Apip Badarudin, ST., MT.
    , Editor: Erlin Arvelina

Download...