Studi Pengaruh Jarak Pengukuran Resistansi Elektroda Pembumian Terhadap Hasil Pengukuran Di Lab. SDTL Polban
Study Of Grounding Electrode Resistance Measurement Distance Impact For Measurement Result At Lab. SDTL Polban
Tugas Akhir, 044 / 2015 / TLIUndergraduate Theses from JBPTPPOLBAN / 2018-07-06 15:52:49
Oleh : Sabit Parid - 121321028 (sabitparid@gmail.com)
Dibuat : 2018-07-06, dengan 4 file
Keyword : Pembumian, Elektroda Pembumian
Subjek : Grounding, Earthing Electrode
Dalam teori sebuah pembumian, semakin kecil nilai resistansi pembumian, maka akan semakin bagus untuk sebuah sistem pembumian. Dalam hal pengukuran resistansi elektroda pembumian khususnya metode 3 kutub, ada 2 elektroda bantu yang ditancapkan ke tanah dengan jarak tertentu antar elektrodanya ketika melakukan pengukuran. Dengan melakukan beberapa langkah pengukuran yang merubah jarak dan sudutnya maka akan ada perbedaan hasil. Perbedaan hasil pengukuran pada masing-masing langkah dan sudut tersebut tidak secara signifikan, hanya pada kondisi 2 elektroda bantu jaraknya berdekatan kurang dari 5 m hasilnya jadi error karena elektroda bantu tersebut tidak punya cukup ruang untuk menghasilkan pengukuran yang memuaskan. Kata Kunci: Pembumian, Elektroda Pembumian.
Deskripsi Alternatif :In theory a grounding, the smaller the resistance value of the grounding, the better it will be for a grounding system. In the case of the grounding electrode resistance measurement, especially 3 poles method, there are two auxiliary electrodes are driven into the ground with a certain distance between the electrodes when taking measurements. By doing some of the steps that change the measurement of distance and angle then there will be a difference in the results. Differences in measurement results at each step and the angle did not significantly, only on the condition of two auxiliary electrodes spaced less than 5 m result was error because the auxiliary electrode does not have enough space to produce a satisfactory measurement. Keywords: Grounding, Earthing Electrode.
Beri Komentar ?#(0) | Bookmark
Properti | Nilai Properti |
---|---|
ID Publisher | JBPTPPOLBAN |
Organisasi | |
Nama Kontak | Erlin Arvelina |
Alamat | Jl. Trsn. Gegerkalong Hilir Ds. Ciwaruga |
Kota | Bandung |
Daerah | Jawa Barat |
Negara | Indonesia |
Telepon | 022 201 3789 ext. 168, 169, 239 |
Fax | 022 201 3889 |
E-mail Administrator | erlin.arvelina@polban.ac.id |
E-mail CKO | erlin.arvelina@polban.ac.id |
Print ...
Kontributor...
- Pembimbing 1: Drs. Dwi Asmono, M.Pd.
Pembimbing 2: Sunarto, S.T., M.Eng., Editor: Erlin Arvelina
Download...
File : KELENGKAPAN TA - 121321028.pdf
(358764 bytes)
File : BAB 1 - 121321028.pdf
(169066 bytes)
File : BAB 2 - 121321028.pdf
(364751 bytes)
File : BAB 5 - 121321028.pdf
(170220 bytes)