Uji Performansi Sistem Refrigerasi Kompresi Uap AC Window sebagai Pompa Kalor
Test Performance of vapor compression Refrigeration System AC Window as Heat Pump
Tugas Akhir, 051 / 2012 / RTUUndergraduate Theses from JBPTPPOLBAN / 2014-07-04 11:47:52
Oleh : Santi Sri Rahmayanti - 091611087 (santi.sri.rahmayanti@gmail.com)
Dibuat : 2014-07-04, dengan 4 file
Keyword : Sistem Refrigerasi, AC Window, Pompa kalor, COP carnot ,COP aktual dan efisiensi
Subjek : refrigeration system, AC window, heat pump, COP carnot ,COP actual and efficiency
Kenyamanan thermal merupakan tujuan pengkondisian udara pada suatu kabin atau ruangan sehingga suhu pada kabin atau ruangan tersebut sesuai dengan yang diinginkan. Untuk negara-negara yang memiliki empat musim pengkondisian udara pada suatu ruangan tidak hanya memanfaatkan pendinginan udaranya saja akan tetapi pemanasannya pun dimanfaatkan untuk pengkondisian udaranya. Untuk mengetahui performansi dari proses pendinginan dan pemanasan sistem tersebut maka penulis melakukan uji performansi terhadap sistem AC Window yang diaplikasikan sebagai pompa kalor. Tujuan penulis melakukan penelitian ini yaitu untuk mengetahui performansi sistem refrigerasi kompresi uap pada AC Window yang diaplikasikan sebagai pompa kalor. Hasil yang diperoleh menunjukkan nilai rata-rata temperatur kabin pada proses pendinginan yaitu 22˚C dan untuk proses pemanasan nilai rata-rata temperatur kabin yaitu 27˚C. Nilai rata-rata tekanan discharge pada proses pemanasan yaitu 17,2 bar gauge dan untuk pendinginan yaitu 12,9 bar gauge. Nilai rata-rata tekanan suction pada proses pemanasan yaitu 5,21 bar gauge dan untuk pendinginan yaitu 4,86 bar gauge . Nilai rata-rata COPaktual pada proses pendinginan yaitu 4,52 dan nilai rata-rata COP carnot yaitu 7,55 sehingga nilai rata-rata efisiensi sistem pada proses pendinginan yaitu 60,1%.Sedangkan untuk proses pemanasan rata-rata nilai COP carnot yaitu 6,86dan nilai rata-rata COP aktualyaitu 4,61 sehingga nilai rata-rata efisiensi sistem pada proses pemanasan yaitu 67,2%. Kata Kunci : Sistem Refrigerasi, AC Window, Pompa kalor, COP carnot ,COP aktual dan efisiensi.
Deskripsi Alternatif :Thermal comfort is a purpose of air conditioning treatment that applied on cabin or room in order to make temperature of it can according to the requirement. For several countries that has four seasons, air conditioning treatment is not only to get a cooling benefit, but also to get the heating benefit. To know the performance of cooling and heating system, the writer did take performance test to AC Window system that applied as heat pump. The aim of this research is to know the performance of vapor compression system on AC Window in application as heat pump. The result shows that average temperature value in cooling process is about 22˚C and for heating process is about 27˚C. Average discharge pressure value is about 17.2 bar gauge for heating process and 12.9 bar gauge for cooling process. Average suction pressure value is about 5.21 bar gauge for heating process and 4.86 bar gauge for cooling process. For cooling process, average COPactualvalue is about 4.52 and COPcarnotvalue is about 7.55, so then average system efficiency value of cooling process is about 60.1%.For heating process average COP carnot value is about 6.86 and average COP actual value is about 4.61,so then average system efficiency value of heating process is about 67.2%. Keywords : refrigeration system, AC window, heat pump, COP carnot ,COP actual and efficiency
Beri Komentar ?#(0) | Bookmark
Properti | Nilai Properti |
---|---|
ID Publisher | JBPTPPOLBAN |
Organisasi | |
Nama Kontak | Erlin Arvelina |
Alamat | Jl. Trsn. Gegerkalong Hilir Ds. Ciwaruga |
Kota | Bandung |
Daerah | Jawa Barat |
Negara | Indonesia |
Telepon | 022 201 3789 ext. 168, 169, 239 |
Fax | 022 201 3889 |
E-mail Administrator | erlin.arvelina@polban.ac.id |
E-mail CKO | erlin.arvelina@polban.ac.id |
Print ...
Kontributor...
- Pembimbing 1: Rudi Rustandi, ST., M.Eng.
Pembimbing 2: Triaji Pangripto Pramudantoro, ST., M.Eng.
, Editor: Erlin Arvelina
Download...
File : DAFTAR - 091611087.pdf
(1005566 bytes)
File : BAB 1 - 091611087.pdf
(269794 bytes)
File : BAB 2 - 091611087.pdf
(762924 bytes)
File : BAB 5 - 091611087.pdf
(309182 bytes)