Analisis Performansi Air-Cooled Water Chiller Alva Laval PC 04 Ph Pada Mesin Pembuat Nitrogen Cair Di PSTNT-Batan Bandung

Performace Analysis Of Air-Cooled Water Chiller Alva Laval PC 04 Ph At Machine Of Liquid Nitrogen In PSTNT-Batan Bandung

Tugas Akhir, 036 / 2014 / RTU
Undergraduate Theses from JBPTPPOLBAN / 2018-04-20 09:53:30
Oleh : Ulfiana Nafiza Izdihar - 111611062 (ulfiananafiza@gmail.com)
Dibuat : 2018-04-20, dengan 4 file

Keyword : Nitrogen cair, Performansi water chiller, Kapasitas pendinginan
Subjek : Liquid Nitrogen, Water Chiller Performance, Cooling Capacity

Nitrogen cair digunakan sebagai bagian dari perawatan detektor spektometer sinar gamma dan ED XRF Epsilon 5 di PSTNT-BATAN. Pada proses pembuatan nitrogen cair diperlukan water chiller untuk mendinginkan air pendingin cryogenerator. Kinerja water chiller dapat mempengaruhi performansi sistem pembuatan nitrogen cair. Pada tugas akhir ini dilakukan pengujian pada water chiller. Berdasarkan buku manual "Liquid Nitrogen PLN 106S" temperatur air yang didinginkan oleh water chiller minimal 5⁰C dan maksimal 25⁰C serta kapasitas pendinginan sebesar 11 kW dengan debit air 0,75 m³/h. Sementara temperatur air yang didinginkan diatur 9,8⁰C hingga 10,8⁰C dan temperatur air yang terukur berkisar 10,1⁰C hingga 10,8⁰C. Terjadi kenaikan dan penurunan daya kompresor berkisar 4,15 kW hingga 4,20 kW. Nilai COP aktual berada diantara 3,35 hingga 3,57 dan nilai COP carnot berada diantara 5,64 hingga 5,95. Nilai effisiensi berada diantara 57,36 % hingga 63,32 %. Pada sistem, kapasitas pendinginan sisi air berada pada 7,89 kW hingga 9,38 kW. Beban ini masih dapat ditangani oleh sistem karena kapasitas pendinginan sistem sebesar 13,90 kW hingga 14,99 kW. Debit air yang terukur sebesar 0,4 m³/h hingga 0,47 m³/h, hal ini mempengaruhi besarnya kapasitas pendinginan dari sisi air. Kata kunci: Nitrogen cair, Performansi water chiller, Kapasitas pendinginan.

Deskripsi Alternatif :

The liquid nitrogen is used as a part of maintenance of gamma-ray spectometer detector and ED XRF Epsilon 5 in PSTNT-BATAN. In the process of making liquid nitrogen, it needs a water chiller to absorb heat from cryogenerator. Water chiller performance can affect the performance of system for making the fluid nitrogen. In this final project water chiller performance was tested. Based on of "Liquid Nitrogen PLN 106S manual book", the water temperature which is chilled by water chiller is designed at minimum temperature of 5⁰C and maximum temperature of 25⁰C and the cooling capacity is 11 kW with waterflow rate of 0,75 m3/h. Meanwhile the chilled water temperature is set from 9,8⁰C until 10,8⁰C and water temperature that is measured is from 10,1⁰C until 10,8⁰C. There are variation in power from 4,15 kW until 4,20 kW. Actual COP is varying from 3,35 to 3,57 and the carnot COP is varying from 5,64 to 5,95. Efficiency value is ranging from 57,36 % to 63,32 %. In the system, the cooling capacity of water is varying from 7,89 kW to 9,38 kW. This cooling load can be handled by the system due to cooling capacity which varied from 13,90 kW to 14,99 kW. Waterflow rate which is measured is ranging from 0,4 m3/h to 0,47 m3/h, which affected the cooling capacity of water. Keywords: Liquid Nitrogen, Water Chiller Performance, Cooling Capacity.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakErlin Arvelina
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorerlin.arvelina@polban.ac.id
E-mail CKOerlin.arvelina@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: Rudi Rustandi, S.T., M.Eng.

    Pembimbing 1: Ir. Eddy Erham, M.T., Editor: Erlin Arvelina

Download...