Path: Top > Tugas Akhir - D3 > Jurusan Teknik Elektro > Program Studi Teknik Listrik > 2016
Evaluasi Konsumsi Energi Listrik Di Pt. Perusahaan Daerah Air Minum Tirta Raharja Melalui Audit Rinci
Evaluation of The Consumption of Electrical Energy at PT Perusahaan Daerah Air Minum Tirta Raharja with Detail Audit
Tugas Akhir, 003 / 2016 / TLIUndergraduate Theses from JBPTPPOLBAN / 2017-08-04 15:21:06
Oleh : Yusal Lukmanul Hakim 131321064 (yusallh@gmail.com)
Dibuat : 2017-08-04, dengan 4 file
Keyword : konsumsi energi listrik, cos phi, harmonisa, THDv, THDi, kapasitor bank
Subjek : The Consumption Of Electrical Energy, Cos Phi, Harmonics, Thdv, Thdi, Capacitor Bank
Konsumsi energi listrik adalah besarnya penggunaan energi listrik yang digunakan oleh pihak konsumen. Beberapa parameter konsumsi energi listrik yang berpengaruh terhadap efisiensi energi diantaranya tegangan tidak seimbang, faktor daya, dan harmonisa. Oleh karena itu perlu diketahui konsumsi energi listrik di PT PDAM Tirta Raharja dengan melakukan audit rinci. Dari hasil pengukuran dan perhitungan yang dilakukan pada panel utama, panel distribusi, dan panel intake didapatkan nilai ketidakseimbangan tegangan pada panel utama sebesar 0,081%, pada panel distribusi sebesar 0,095% dan pada panel intake sebesar 0,49%. Besarnya ketidakseimbangan tegangan yang dipersyaratkan oleh NEMA memberikan rekomendasi bahwa Vunbalance maksimum adalah 1%. Untuk harmonisa arus didapatkan nilai THDI pada panel utama sebesar 2,5%, pada panel distribusi sebesar 4,2% dan pada panel intake sebesar 3,8%. Nilai tersebut masih berada dibawah 15% (sesuai standar IEEE 519-1992). Dan untuk harmonisa tegangan didapatkan nilai THDV pada panel utama sebesar 1,3%, pada panel distribusi sebesar 1.43% dan pada panel intake sebesar 1,8%. Nilai tersebut masih berada dibawah 5% (sesuai standar IEEE 519-1992). Untuk faktor daya didapatkan nilai cos phi pada panel utama sebesar 0,825, maka diperlukan perbaikan faktor daya menjadi 0,9 dengan cara melakukan pemasangan kapasitor bank secara global compensation yang dipasang secara paralel dengan panel utama sebesar 6 kVAR dengan 4 step. Sedangkan pada panel distribusi nilai cos phi sebesar 0,828 dan pada panel intake sebesar 0,829, maka diperlukan perbaikan faktor daya menjadi 0,95 dengan cara melakukan pemasangan kapasitor bank secara individual compensation yang dipasang paralel dengan panel distribusi dan intake. Dengan kapasitor bank sebesar 3 kVAR untuk panel distribusi, dan 6,5 kVAR untuk panel intake. Kata kunci : konsumsi energi listrik, cos phi, harmonisa, THDv, THDi, kapasitor bank
Deskripsi Alternatif :The consumption of electrical energy is the amount of electrical energy used by the consumer. Some of the electrical energy consumption parameters that affect energy efficiency such unbalanced voltage, power factor, and harmonics. Therefore, we have to know the consumption of electrical energy at PT PDAM Tirta Raharja by conducting a detailed audit. From the results of measurements and calculations performed on the main panel, distribution panels, and intake panel voltage unbalance values obtained on the main panel is 0.081%, on the distribution panel is 0.095%, and on the intake panel is 0.49%. The amount of unbalance voltage required by NEMA recommends that Vunbalance maximum is 1%. for harmonic current, THDi value on the main panel was 2.5%, on the distribution panel is 4.2% and on the intake panel is 3.8%. This value is still below 15% (according to standard IEEE 519-1992). And for harmonic voltage, the value THDV on the main panel is 1.3%, on the distribution panel was 1.43% and on the intake panel is 1.8%. This value is still below 5% (according to standard IEEE 519-1992). For power factor, values of cos phi obtained in the main panel is 0.825, then the required power factor improvement to 0.9 by doing the installation of capacitor banks globally compensation mounted in parallel with the main panel of 6 KVAR with 4 step. While on the distribution panel cos phi value is 0.828 and on the intake panel is 0,829, it is necessary to 0.95 power factor improvement by doing the installation of individual compensation capacitor bank in parallel with the distribution panel and intake. With a capacitor bank for 3 KVAR to the distribution panel, and 6.5 KVAR for intake panel. Keywords: the consumption of electrical energy, cos phi, harmonics, THDv, THDi, capacitor bank
Beri Komentar ?#(0) | Bookmark
Properti | Nilai Properti |
---|---|
ID Publisher | JBPTPPOLBAN |
Organisasi | |
Nama Kontak | Erlin Arvelina |
Alamat | Jl. Trsn. Gegerkalong Hilir Ds. Ciwaruga |
Kota | Bandung |
Daerah | Jawa Barat |
Negara | Indonesia |
Telepon | 022 201 3789 ext. 168, 169, 239 |
Fax | 022 201 3889 |
E-mail Administrator | erlin.arvelina@polban.ac.id |
E-mail CKO | erlin.arvelina@polban.ac.id |
Print ...
Kontributor...
- Pembimbing : Heri Budi Utomo
Pembimbing II : Supriyanto, ST.,MT
, Editor: Muhammad Abdillah Islamy, S.Pd
Download...
File : KELENGKAPAN TA - 131321064.pdf
(551019 bytes)
File : BAB 1 - 131321064.pdf
(435897 bytes)
File : BAB 2 - 131321064.pdf
(577528 bytes)
File : BAB 5 - 131321064.pdf
(243697 bytes)