Perhitungan Rugi-Rugi Pada Transformator Akibat Harmonisa dan Perancangan Filter Pasif Menggunakan Matlab

Calculation of Loss on Transformers Due to Harmonization And Passive Filter Design using Matlab

Tugas Akhir, 005 / 2021 / TLI
Undergraduate Theses from JBPTPPOLBAN / 2023-01-30 10:06:56
Oleh : Elsi Berliani Putri - 181321005 (elsi.berliani.tlis18@polban.ac.id )
Dibuat : 2023-01-30, dengan 4 file

Keyword : Matlab, Perhitungan Rugi-Rugi, Transformator Akibat, Harmonisa, Perancangan, Filter Pasif
Subjek : Matlab, Calculation of Loss, Transformers Due, Harmonization, Passive Filter, Design

Tenaga listrik di Indonesia berada pada frekuensi 50 Hz,dimana komponen yang digunakan pada suatu sitem tenaga merupakan transformator, timbulnya harmonisa disebabkan karena pengoperasian beban listrik non linier. Total Harmonic Distortion (THD) pada transformator berpotensi menimbulkan losses yang sangat berpengaruh terhadap efisiensi transformator, dalam penelitian ini dilakukan pengukuran THD Transformator GR088 di Penyulang Menjangan selanjutnya dibandingkan dengan hasil THD pada simulink MATLAB yang di lakukan. THDv berdasarkan hasil pengukuran yaitu sebesar 5,2% dan berdasarkan hasil simulasi yaitu sebesar 2,69% THDi berdasarkan hasil dari pengukuran yaitu sebesar 0,8% dan hasil dari simulasi dari THDi yaitu 4,38%. Berdasarkan analisis losses yang dihitung sebelum harmonisa sebesar 2,98 kW. Akibat adanya pengaruh harmonisa sehingga menyebabkan terjadinya peningkatan menjadi 4,036 kW, dengan pemakaian filter pasif THDi mengalami penurunan sehingga THD memenuhi standart IEEE 519-1992 THD arus setelah pemakaian filter sebesar 4,38% metode yang digunakan yaitu perhitungan rugi-rugi pada transformator dan perancangan filter pasif harmonisa terhadap perangkat lunak MATLAB. tujuan tugas akhir ini dibuat mengalami gimana rugi-rugi yang terjalin pada transformator mengetahui hasil perbandingan THD pada dikala perhitungan serta pengukuran dikala perancangan akumulasi filter pasif buat melakukan simulink MATLAB.

Deskripsi Alternatif :

Electric power in Indonesia is at a frequency of 50 Hz, where the component used in a power system is a transformer, the emergence of harmonics is caused by the operation of non-linear electrical loads. Total Harmonic Distortion (THD) in the transformer has the potential to cause losses that greatly affect the efficiency of the transformer, in this study the THD Transformer GR088 measurement in the Menjangan Feeder was then compared with the THD results on the MATLAB simulink that was carried out. THDv based on measurement results is 5.2% and based on simulation results is 2.69% THDi based on measurement results is 0.8% and simulation results from THDi is 4.38%. Based on the analysis of losses calculated before harmonics of 2.98 kW. Due to the influence of harmonics, it causes an increase to 4.036 kW, with the use of passive THDi filters, it decreases so that THD meets the IEEE 519-1992standard, the THDcurrent after using the filter is 4.38%. The method used is the calculation of losses in the transformer and filter design. passive harmonics againstsoftware MATLAB. The purpose of this final project is to explore how the losses that occur in the transformer find out the results of the THD comparison during calculations and measurements when designing passive filter accumulation to perform MATLAB simulinks.

Beri Komentar ?#(0) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakErlin Arvelina
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorerlin.arvelina@polban.ac.id
E-mail CKOerlin.arvelina@polban.ac.id

Print ...

Kontributor...

  • Pembimbing: Ir. Heri Budi Utomo, Editor: Muhammad Abdillah Islamy, S.Pd

Download...