Penyetelan TXV setelah dilakukan proses retrofitting R-22 ke R-404A pada thermal storage untuk penyimpanan tomat

TXV adjustment after retrofitting process R-22 to R-404A in thermal storage for tomato storage

Tugas Akhir, 046 / 2020 / RTU
Undergraduate Theses from JBPTPPOLBAN / 2021-12-17 09:44:59
Oleh : Nabhila Octa Herviani - 171611052 (nabhilaocta23@gmail.com )
Dibuat : 2021-12-17, dengan 4 file

Keyword : Thermal storage system, Retrofit, and Rotation of TXV adjustment, COP, Efficiency, also Consumption of Electical Energy
Subjek : Sistem Thermal Storage, Retrofit, dan derajat penyetelan TXV, COP, Efisiensi, serta Konsumsi Energi Listrik

Refrigeran jenis HCFC (hydrochloroflourocarbon) merupakan jenis refrigeran yang sudah tidak diizinkan untuk diproduksi, diedarkan, dan dipergunakan pada sistem refrigerasi, baik untuk keperluan industri maupun komersil. Hal ini telah diatur dalam peraturan yang dikeluarkan oleh Menteri Perindustrian Republik Indonesia Nomor: 41/M-IND/PER/5/2014 mengenai larangan penggunaan HCFC (hydrochlorofluorocarbon), dikarenakan refrigeran jenis HCFC memiliki dampak besar dalam kerusakan lingkungan. Sehingga diperlukan alternatif refrigeran jenis lain yang lebih ramah lingkungan. Pada penelitian ini dilakukan proses retrofit dari R-22 ke R-404A dengan melakukan penyetelan TXV (Thermostatic Expansion Valve) yang bertujuan untuk mengetahui putaran optimal pada TXV agar R-404 memiliki performansi mendekati R-22. Alat yang digunakan untuk penelitian ini berupa sistem thermal storage untuk penyimpanan produk tomat dengan kapasitas kompresor ½ Pk dan 15% larutan CaCl sebagai refrigeran sekundernya. Variasi putaran TXV berturut-turut yaitu saat kondisi TXV normal, 45° berlawanan arah jarum jam dan 45° searah jarum jam. COP refrigeran R-22 memiliki nilai 3,41 sedangkan untuk R-404A memiliki nilai COP 2,48; 2,53; dan 2,42. Efesiensi sistem refrigerasi pada refrigeran R-22 memiliki nilai sebesar 79,47% sedangkan untuk R-404A memiliki nilai 59,83%; 61,07%; dan 60,68%. Dan konsumsi energi listrik R-22 memiliki nilai 1,89 kWh sedangkan R-404A memiliki nilai 0,96 kWh; 0,947 kWh; dan 0,939 kWh. Hasil penelitian ini menunjukkan bahwa penyetelan TXV dapat mempengaruhi efisiensi sistem dan putaran yang hampir mendekati performansi R-22 adalah saat diputar 45° berlawanan arah jarum jam.

Deskripsi Alternatif :

HCFC (hydrochloroflourocarbon) refrigerant is a type of refrigerant that is no longer permitted to be produced, circulated, and used in refrigeration systems for both industrial and commercial purpose. This has been regulated in a regulation issued by the Minister of Industry of the Repubic of Indonesia Number: 41/M-IND/PER/5/2014 regarding the prohibition of using HCFC (hydrochloroflourocarbon), because HCFC refrigerant have a big impact on environmental damage. So it requires other types of refrigerant alternatives that are more enviromentally friendly. In this research, a retrofit process from R-22 to R-404A was carried out by adjusting TXV (Thermostatic Expansion Valve) which aims to determine the optimal rotation of the TXV so that the R-404A has a performance approaching R-22. Thermal storage system with compresor capacity ½ Pk which is used for tomato storage and has 15% CaCl as secondary refrigerant. The variation of TXV rotation used were when TXV in a normal condition,45° counterclockwise and 45° clockwise. COP refrigerant R-22 has a value of 3.41 while for R-404A it has a COP value of 2.48; 2.53; and 2.42. The efficiency of the refrigeration system in R-22 has a value of 79.47% while for R-404A it has a value of 59.83%; 61.07%; and 60.68%. And the energy consumption of R-22 has value of 1.89 kWh while R-404A has value of 0.96 kWh; 0.947 kWh; and 0.939 kWh. The result showed that TXV adjustment can affect the efficiency of the system and the rotation of TXV is almost close to the R-22 performance when rotated 45° counterclockwise.

Beri Komentar ?#(3) | Bookmark

PropertiNilai Properti
ID PublisherJBPTPPOLBAN
Organisasi
Nama KontakErlin Arvelina
AlamatJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
KotaBandung
DaerahJawa Barat
NegaraIndonesia
Telepon022 201 3789 ext. 168, 169, 239
Fax022 201 3889
E-mail Administratorerlin.arvelina@polban.ac.id
E-mail CKOerlin.arvelina@polban.ac.id

Print ...

Kontributor...

  • Pembimbing 1: Triaji Pangripto Pramudantoro, S.T., M.Eng.


    Pembimbing 2: Ir. Arda Rahardja Lukitobudi, M.Eng., Editor: Muhammad Abdillah Islamy, S.Pd

Download...