Pengaruh Variasi Kecepatan Fan Kondenser Pada Sistem Refrigerasi Kompresi Uap
The Effect Of Condenser Fan Speed Variation On The Steam Compression Refrigeration System
Tugas Akhir, 047 / 2020 / RTUUndergraduate Theses from JBPTPPOLBAN / 2021-12-17 09:49:11
Oleh : Nadhif Nugraha Siswanto - 171611053 (nadhif.nugraha.tptu17@polban.ac.id )
Dibuat : 2021-12-17, dengan 4 file
Keyword : variations, COP, fan, condenser
Subjek : variasi, COP, fan, kondenser
Pada saat ini sistem refrigerasi kompresi uap sudah sangat umum digunakan, seperti keperluan industri, rumah tangga dan lain â lain. Sistem refrigerasi juga sudah memiliki banyak jenis refrigerant yang ramah lingkungan seiring perkembangannya jaman. Pada tugas akhir ini digunakan refrigerant R 404a dan kompresor jenis hermetic dengan kapasitas ½ PK, pada setiap pengambilan data kecepatanfan pada condenser akan divariasikan dengan 4 jenis variasi yaitu variasi kecepatan fan1 (7.212 RPM), variasi kecepatan fan2 (6.723 RPM), variasi kecepatan fan 3 (2.362 RPM) dan variasi kecepatan fan 4 (1.013 RPM). Pengambilan data dilakukan tergantung variasi kecepatan fan nya, dan setiap variasi akan diambil data 5 menit sekali. Hal ini dilakukan untuk melihat pengaruh variasi kecepatan fan terhadap kinerja sistem berupa COP (coefesien of performance). Setelah dilakukan pengolahan data nilai COPaktualtertinggi yaitu pada variasi 1 dengan nilai 3.18 dan COPaktual terendah pada variasi 4 dengan nilai 2.34.
Deskripsi Alternatif :At this time vapor compression refrigeration systems are very commonly used, such as industrial, household and other purposes. The reference system also has many types of refrigerants that are environmentally friendly as the times go on. In this final project used refrigerant R 404a and compressor type hermetic with a capacity of ½ PK, at each data collection fan speed on the condenser will be varied with 4 types of variations, namely variation 1 (7.212 RPM), variation 2 (6.723 RPM), variation 3 (2.362 RPM) and variation 4 (1.013 RPM). Data collection will be carried out depending on the variation, and for each variation data will be taken every 5 minutes. This is done to see the effect of fan speed variations on system performance in the form of COP (coefficient of performance. After processing data, the highest actual COP value is in variation 1 with a value of 3.18 and the lowest actual COP is in variation 4 with a value of 2.34.
Beri Komentar ?#(2) | Bookmark
Properti | Nilai Properti |
---|---|
ID Publisher | JBPTPPOLBAN |
Organisasi | |
Nama Kontak | Erlin Arvelina |
Alamat | Jl. Trsn. Gegerkalong Hilir Ds. Ciwaruga |
Kota | Bandung |
Daerah | Jawa Barat |
Negara | Indonesia |
Telepon | 022 201 3789 ext. 168, 169, 239 |
Fax | 022 201 3889 |
E-mail Administrator | erlin.arvelina@polban.ac.id |
E-mail CKO | erlin.arvelina@polban.ac.id |
Print ...
Kontributor...
- Pembimbing 1: Tandi Sutandi, S.ST., M.T.
Pembimbing 2: Triaji Pangripto Pramudantoro, S.T., M.Eng., Editor: Muhammad Abdillah Islamy, S.Pd
Download...
File : KELENGKAPAN TA - 171611053.pdf
(756652 bytes)
File : BAB 1 - 171611053.pdf
(272754 bytes)
File : BAB 2 - 171611053.pdf
(367869 bytes)
File : BAB 5 - 171611053.pdf
(164717 bytes)