Path: Top > Tugas Akhir - D3 > Jurusan Teknik Elektro > Program Studi Teknik Listrik > 2013

Rancang Bangun Modul Praktikum pengujian Karakteristik dan Simulasi Setting Proteksi Over and Under Voltage Generator AC meggunakan Rele MH OUV 400

Design and Build Practical Module of Over and Under Voltage Generator AC using MH OUV 400 Relay

Tugas Akhir, 006 / 2013 / TLI
Undergraduate Theses from JBPTPPOLBAN / 2017-04-28 11:37:23
By : Novian Listanti - 101321057 (novian.listanti@gmail.com)
Created : 2017-04-28, with 4 files

Keyword : OVR, UVR, generator, setting relay
Subject : OVR, UVR, generator, relay settings

Kestabilan catu daya listrik dalam suatu sistem rangkaian listrik sangat diperlukan. Adanya gangguan dalam catu daya listrik dapat mempengaruhi bahkan merusak suatu sistem rangkaian listrik. Didalam generator biasanya sudah dilengkapi dengan pengatur tegangan otomatis AVR (Automatic Voltage Regulator), yang akan mengatur kestabilan tegangan keluarannya. Namun demikian untuk mengantisipasi jika pengatur tegangan otomatis AVR (Automatic Voltage Regulator) gagal bekerja, dan terjadi gangguan pada generator yang menyebabkan generator ada pada kondisi abnormal maka rele tegangan lebih (over voltage relay) dan rele tegangan kurang (under voltage relay) digunakan sebagai pengaman dari gangguan tersebut . Rele tegangan lebih (over voltage relay) dan rele tegangan kurang (under voltage relay) yang digunakan dilengkapi dengan piranti tunda waktu (time delay) agar diperoleh selektivitas yang memadai, khususnya untuk koordinasi dengan karakteristik pengatur tegangan otomatis. Rele tegangan lebih dan tegangan kurang tipe MH OUV 400 bekerja pada tegangan sistem 220 Volt dan dengan setting tegangan untuk OVR adalah 105% dari tegangan nominal dan untuk UVR 90% dari tegangan nominal. Rele ini bekerja berdasarkan kenaikan dan penurunan tegangan melebihi atau mencapai setting yang telah ditentukan. Pengujian yang dilakukan terhadap rele tegangan lebih dan tegangan kurang ini ditujukan untuk membuktikan karakteristik rele yaitu definite time serta mengetahui kerja dari rele tersebut dalam mengatasi gangguan tegangan lebih pada generator yang disebabkan oleh overspeed akibat lepasnya beban dan gangguan tegangan kurang pada generator akibat beban lebih. Data-data dari hasil pengujian yang telah dilakukan menunjukan bahwa rele ini bekerja sesuai dengan manual book. Kata kunci: OVR, UVR, generator, setting relay.

Description Alternative :

The stability of the electric power supply system in an electrical circuit is needed. A disturbance in the power supply can affect even damage an electrical circuit system. Inside the generator are usually equipped with AVR (Automatic Voltage Regulator), which will regulate the output voltage stability. However, to anticipate if the automatic voltage regulator AVR (Automatic Voltage Regulator) failed to work, and an interruption in the generator which causes the generator is in the abnormal condition of overvoltage or undervoltage then over and under voltage relay is used as a protec of the disorder. Over voltage relay and under voltage relay equipped with a device that used a time delay in order to obtain sufficient selectivity, particularly for coordination with the characteristics of the automatic voltage regulator. Over voltage relay and under voltage relay type MH OUV 400 works on 220 volts and with the voltage setting for OVR is 105% than the nominal voltage and to UVR 90% of nominal voltage. This relay works based on the increase and decrease voltage exceeds or reaches specified setting. Tests performed on the over voltage and less voltage relay is intended to prove the relay is definite time characteristics and to know the work of relay in overcoming interference over voltage on the generator caused by overspeed due to release of load and interference less voltage caused by over load. Datas obtained from testing indicates that this relay works appropriate with manual book. Keywords: OVR, UVR, generator, relay settings.

Give Comment ?#(1) | Bookmark

PropertyValue
Publisher IDJBPTPPOLBAN
Organization
Contact NameErlin Arvelina
AddressJl. Trsn. Gegerkalong Hilir Ds. Ciwaruga
CityBandung
RegionJawa Barat
CountryIndonesia
Phone022 201 3789 ext. 168, 169, 239
Fax022 201 3889
Administrator E-mailerlin.arvelina@polban.ac.id
CKO E-mailerlin.arvelina@polban.ac.id

Print ...

Contributor...

  • Pembimbing 1: Ir. Hari Purnama, M.Eng.

    Pembimbing 2: Drs. Dwi Asmono, M.Pd., Editor: Erlin Arvelina

Downnload...